Plan Review Notes For Permit 07020094
Permit Number 07020094
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-13 10:15:26DENIED;
 1. SHOW CLEAR FLOOR SPACE FOR LAVATORY ON FLOOR PLAN.
 2. INTERIOR ELEV. "D", CENTER LINE OF TOILET SHALL BE
 18" OFF WALL NOT 24".
 3. INTERIOR ELEV. "B" HEIGHT OF LAVATORY TO THE RIM CAN
 BE 34". IF YOU MOUNT LAV AT 30" YOU MAY NOT HAVE THE
 27" REQUIRED FOR KNEE CLEARANCE .
 4. WALL FINISH WITHIN 2' OF THE WATER CLOSET SHALL HAVE
 A SMOOTH HARD NONABRORBENT SURFACE. FBC-2004 BUILDING
 SECTION 1210.2.