Plan Review Notes
Plan Review Notes For Permit 07020094
Permit Number 07020094
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-13 06:25:48BUILDING PLAN REVIEW
 PERMIT:07020094
 ADD:1101 CHARLES STREET
 CONT: LANCE H. MOONEY
 TEL: (561)747-4643
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO COPIES OF THE
 PRODUCT APPROVALS FOR THE NEW DOOR.
  
 3)FBC. 1210.2WALLS WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT AVERSELY
 AFFECTED BY MOISTURE.
  
 4)THE H.C. GRAB BARS ON THE BACK WALL SHALL BE
 INSTALLED IN ACCORDANCE WITH FBC. CH. 11.FIG30E.THE
 GRAB BAR ON THE BACK WALL SHALL BE 6 INCHES MAX FROM
 THE SIDE WALL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726