Notes
Date Text
2007-06-19 16:38:48*** UNSAT 2ND REVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SUBMIT TWO SET OF PLANS AND SUPPORTING
 DOCUMENTS. PLEASE BE SURE EACH PACKAGE IN PLACED INTO
 BOUND SETS AND SHEETS ARE NOT SUBMITTED LOOSELY.
 FBC 106.1
  
 2) NOTE: PLEASE SEE THE SUBMITTED LETTERS FOR SIGNATURE
 VERIFICATIONS DO NOT CONTAIN THE COMPLETEDNOTARY
 INFORMATION AS REQUIRED UNDER FS 117.05.
  
 3) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 4) NOTE: PLEASE SEE RISER SHOWS TAPPED CONDUCTORS FROM
 A J-BOX/GUTTER TO EACH ATS DEVICE. PLEASE SEE 240.21 AS
 TAPS ARE REQUIRED TO TERMINATE IN OVER CURRENT
 PROTECTION. PLEASE SEE THE SPECS SUBMITTED FOR THE ATS
 EQUIPMENT DOES NOT INDICATE ANY OCP/ MAIN BREAKERS FOR
 THE TAPPED FEEDERS FROM THE GUTTER. PLEASE SEE 408.36
 AND PLEASE ALSO SEE THE NEXT COMMENT.
  
 5) NOTE:THIS COMMENT IS THE SAME FROM PREVIOUS REVIEW
 AS INFORMATION ABOVE IS NOT CLEAR. PLEASE SEE 702.11 AS
 A DISCONNECTING MEANS PER 225.31-225.39 WILL BE
 REQUIRED AS THE BREAKER ON THE GENERATOR MAY NOT BE
 USED AS PER ZONING COMMENTS THIS MAY REQUIRE A
 WALL/FENCING ETC WHICH WILL NOT ALLOW READY ACCESS AND
 IF THE BREAKER ON THE GENERATOR IS NOT WITHIN SIGHT
 (50FT) READILY ACCESSIBLE, (NOT LOCKED) ETC THEN
 DISCONNECTING MEANS IS REQUIRED. PLEASE SEE NOTE ABOVE
 AS THIS WILL AFFECT THE TAPS FROM THE GENERATOR J-BOX
 WHICH REQUIRES THE CONDUCTORS TO TERMINATE IN OCP.
 PLEASE SEE DISCONNECTS FROM THE GEN BEFORE ATS MAY BE
 ONE SOLUTION OR ATS FOR ENTIRE SERVICE WHICH WILL BE
 REQUIRED TO BE SE RATED AND DISCONNECTING MEANS FOR
 FEEDERS FROM GEN.
 THESE ARE IN NO WAY THE ONLY SCENARIO.
  
 6) NOTE: PLEASE KNOW AS THE VALUE WAS INCREASED THERE
 ARE FEES OWED WHICH WILL BE REQUIRED TO BE PAID BEFORE
 PLANS CAN BE RE-SUBMITTED FOR REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]