| 2007-06-19 16:38:48 | *** UNSAT 2ND REVIEW ** |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO SET OF PLANS AND SUPPORTING |
| | DOCUMENTS. PLEASE BE SURE EACH PACKAGE IN PLACED INTO |
| | BOUND SETS AND SHEETS ARE NOT SUBMITTED LOOSELY. |
| | FBC 106.1 |
| | |
| | 2) NOTE: PLEASE SEE THE SUBMITTED LETTERS FOR SIGNATURE |
| | VERIFICATIONS DO NOT CONTAIN THE COMPLETEDNOTARY |
| | INFORMATION AS REQUIRED UNDER FS 117.05. |
| | |
| | 3) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC). |
| | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE |
| | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR |
| | REVIEWER(S). |
| | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH |
| | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD |
| | BE REVISED ACCORDINGLY. |
| | |
| | 4) NOTE: PLEASE SEE RISER SHOWS TAPPED CONDUCTORS FROM |
| | A J-BOX/GUTTER TO EACH ATS DEVICE. PLEASE SEE 240.21 AS |
| | TAPS ARE REQUIRED TO TERMINATE IN OVER CURRENT |
| | PROTECTION. PLEASE SEE THE SPECS SUBMITTED FOR THE ATS |
| | EQUIPMENT DOES NOT INDICATE ANY OCP/ MAIN BREAKERS FOR |
| | THE TAPPED FEEDERS FROM THE GUTTER. PLEASE SEE 408.36 |
| | AND PLEASE ALSO SEE THE NEXT COMMENT. |
| | |
| | 5) NOTE:THIS COMMENT IS THE SAME FROM PREVIOUS REVIEW |
| | AS INFORMATION ABOVE IS NOT CLEAR. PLEASE SEE 702.11 AS |
| | A DISCONNECTING MEANS PER 225.31-225.39 WILL BE |
| | REQUIRED AS THE BREAKER ON THE GENERATOR MAY NOT BE |
| | USED AS PER ZONING COMMENTS THIS MAY REQUIRE A |
| | WALL/FENCING ETC WHICH WILL NOT ALLOW READY ACCESS AND |
| | IF THE BREAKER ON THE GENERATOR IS NOT WITHIN SIGHT |
| | (50FT) READILY ACCESSIBLE, (NOT LOCKED) ETC THEN |
| | DISCONNECTING MEANS IS REQUIRED. PLEASE SEE NOTE ABOVE |
| | AS THIS WILL AFFECT THE TAPS FROM THE GENERATOR J-BOX |
| | WHICH REQUIRES THE CONDUCTORS TO TERMINATE IN OCP. |
| | PLEASE SEE DISCONNECTS FROM THE GEN BEFORE ATS MAY BE |
| | ONE SOLUTION OR ATS FOR ENTIRE SERVICE WHICH WILL BE |
| | REQUIRED TO BE SE RATED AND DISCONNECTING MEANS FOR |
| | FEEDERS FROM GEN. |
| | THESE ARE IN NO WAY THE ONLY SCENARIO. |
| | |
| | 6) NOTE: PLEASE KNOW AS THE VALUE WAS INCREASED THERE |
| | ARE FEES OWED WHICH WILL BE REQUIRED TO BE PAID BEFORE |
| | PLANS CAN BE RE-SUBMITTED FOR REVIEW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |