2007-02-16 16:31:38**FAILED**
  
 1) AS THE GENERATOR IS PROPOSED TO BE PLACED IN THE
 PARKING AREA, PLEASE SHOW THE NUMBER OF PARKING SPACES
 PROVIDED BEFORE, AND AFTER THE INSTALLATION OF THE
 GENERATOR. NOTE THAT YOU ARE REQUIRED TO PROVIDE 11
 PARKING SPACES, INCLUDING ONE HANDICAP ACCESSIBLE
 PARKING SPACE.
  
 2) THE SURVEY MUST BE SIGNED AND SEALED, AND NOT BE
 OLDER THAN 1 YEAR.
  
 3) THE SURVEY MUST BE TO SCALE.
  
 4) THE GENERATOR MUST BE SCREENED AND LANDSCAPED PER
 THE REQUIREMENTS OF SECTION 94-444(B) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.