Plan Review Notes
Plan Review Notes For Permit 07020088
Permit Number 07020088
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-25 11:35:36*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION SUBMITTED
 DOES NOT CONTAIN ORIGINAL SIGNATURES FROM THE
 QUALIFIER, THIS IS IN FACT APPEARS TO BE A COLOR
 PHOTO-COPY AND APPLICATION WILL BE RETAINED. PLEASE SEE
 FS 117.5 FOR NOTARIES WHICH PROHIBIT A NOTARY TO
 NOTARIZE A SIGNATURE OR LEGAL DOCUMENT WHICH IS NOT
 ORIGINAL.
 PLEASE KNOW THAT THE PLANS AND PERMIT APPLICATION WILL
 NOT BE RELEASED BY THIS OFFICE.
 THIS MAY BE TURNED OVER TO THE GOVERNOR'S BOARD AND
 ECLB.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES. DOCUMENTATION SUCH AS SIGNED AND SEALED
 PLANS, PERMIT APPLICATION IS REQUIRED TO CONTAIN
 ORIGINAL SIGNATURES. THESE LAWS WERE IMPLEMENTED TO
 PROTECT THE CONTRACTOR.
  
 ** THERE HAVE BEEN SEVERAL CASES OF PERMIT APPLCATIONS
 BEING SUBMITTED FOR WORK BY OTHER THAN THE CONTRACTOR
 FOR RECORD WITHOUT KNWOLEDGE OF CONTRACTOR. THIS AHJ
 CURRENTLY HAS NUMEROUS SUCH CASES WITH THE CLB, ECLB.
  
 2) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 3) NOTE: PLEASE SEE THE SITE PLANS WHICH MENTIONS THE
 GENERATOR IS LOCATED 5FT FROM PROPERTY LINE, HOWEVER
 BASED ON THE SITE PLAN PROVIDED, THIS IS NOT THE CASE.
 PLEASE SCALE AND SHOW ALL SET BACKS AND LOCATIONS OF
 ANY ADJACENT BUILDINGS LOCATED ON THE PROPERTY NEXT TO
 THIS PROPERTY.
 PLEASE SEE ZONING COMMENTS ALSO.
  
 4) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH
 REFLECT A 300AMP BREAKER FEEDING UNITS, WHERE PLANS
 INDICATE A 350AMP BREAKER AT THIS SAME LOCATION FOR THE
 GENERATOR? PLEASE CORRELATE AND ADJUST AS NEEDED. FBC
 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 4) NOTE: PLEASE SEE RISER SHOWS TAPPED CONDUCTORS FROM
 A J-BOX TO EACH ATS DEVICE. PLEASE SEE 240.21 AS TAPS
 ARE REQUIRED TO TERMINATE IN OVER CURRENT PROTECTION.
 PLEASE ALSO SEE THE NEXT COMMENT.
  
 5) NOTE: PLEASE SEE 702.11 AS A DISCONNECTING MEANS PER
 225.31-225.39 WILL BE REQUIRED AS THE BREAKER ON THE
 GENERATOR MAY NOT BE USED AS PER ZONING COMMENTS THIS
 MAY REQUIRE A WALL/FENCING ETC WHICH WILL NOT ALLOW
 READY ACCESS AND IF THE BREAKER ON THE GENERATOR IS NOT
 WITHIN SIGHT (50FT) READILY ACCESSIBLE, (NOT LOCKED)
 ETC THEN DISCONNECTING MEANS IS REQUIRED. PLEASE SEE
 NOTE ABOVE AS THIS WILL AFFECT THE TAPS FROM THE
 GENERATOR J-BOX WHICH REQUIRES THE CONDUCTORS TO
 TERMINATE IN OCP.
 PLEASE SEE DISCONNECTS FROM THE GEN BEFORE ATS MAY BE
 ONE SOLUTION OR ATS FOR ENTIRE SERVICE WHICH WILL BE
 REQUIRED TO BE SE RATED AND DISCONNECTING MEANS FOR
 FEEDERS FROM GEN.
 THESE ARE IN NO WAY THE ONLY SCENARIO.
  
 6) NOTE: PLEASE SEE THE SIGNATURE ON THE SLAB
 ENGINEERING PLANS IS ALSO NOT ORIGINAL AND IS A COLOR
 PHOTO-COPY FROM THE ENGINEER WITH A RAISED SEAL. PLEASE
 SEE THAT THIS SAME COMMENT HAS BEEN MADE BY THIS OFFICE
 ON SEVERAL OTHER SETS OF PLANS SUBMITTED WHICH IS
 PROHIBITED UNDER FAC 61G15-23.002 AND FS 471.025.
 PLEASE KNOW THAT THESE WILL BE RETAINED AND PLACED WITH
 PREVIOUS RETAINED PLANS AND FORWARDED TO THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS IF COMPLIANCE IS NOT
 MADE AND THIS PRACTICED IS CONTINUED BY THIS ENGINEER.
 THESE ARE COLORED PHOTO-COPIES.
 THIS COMMENT IS MADE AND REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
 THESE LAWS AND ADMINISTRATIVE CODES WERE PLACED INTO
 LAW TO PROTECT THE ENGINEER AND FIRM.
  
 7) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS EVEN IF MATERIALS ARE OWNER SUPPLIED.
 PLEASE KNOW DEPENDING ON SCOPE OF WORK REQUIRED FOR
 SCREENING BY ZONING, THIS MAY REQUIRE A GC TO PULL
 PERMIT FOR ANY WALL/BUILDING CONSTRUCTION.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]