2007-03-06 15:39:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE INSTALLATION SCHEDULE STATES THAT 1 3/4 INCH
 TAPCONS WILL BE USED.1 3/4 INCH EMBEDMENT REQUIRED,
 WITH STUCCO THIS DOES NOT MEET MINIMUM LENGTH.
  
 2.)DETAILS G AND H ARE INSTALLED INTO POURED
 CONCRETE, BUT YOU SHOW CBS AS THE SUBSTRATE AT THE TOP.
 PLEASE ADDRESS.
  
 3.)PLEASE MARK DETAILS IN INK RATHER THAN HIGHLIGHTER
 AS YELLOW HIGHLIGHTER DOES NOT APPEAR WHEN DIGITIZED,
 AND BLUE AND GREEN HIGHLIGHTER MAKE THE UNDERLYING TEXT
 ILLEGIBLE.
  
  