| Plan Review Notes For Permit 07020065 |
| Permit Number |
07020065 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-17 14:13:10 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) SUBMIT COOLING LOAD CALCULATIONS, SEE | | | 13-607.1.ABC.1. | | | | | | 3) SHOW ON A/C PLANS EQUIPMENT SCHEDULE CONDENSER UNIT | | | MODEL NUMBER AND HEATER KW. | | | | | | 4) SHOW THE SIZE OF THE SUPPLY AIR DUCT ON THE FIRST | | | FLOOR TRUNK LINE TO THE MIXING BOX (SEE YELLOW HIGH | | | LIGHT ON PLANS). | | | | | | 5) THE WATER CLOSET ROOM AT THE MASTER SUITE WILL NEED | | | AN EXHAUST FAN, SEE 2004 FBC/R M1506.3. | | | | | | 6) THE 12" RETURN AIR TRANSFER TO THE MASTER SUITE | | | NEEDS TO BE 18", SEE 2004 FBC/R M1602.4. | | | | | | ALL OF THESE CORRECTIONS HAVE BEEN REQUESTED ON OTHER | | | IDENTICAL HOMES FOR ROSEMARY ACQUISITIONS SUBMITTED TO | | | THIS OFFICE BY SCOTCORP INC.. IN THE FUTURE PLEASE | | | CHECK AND CORRECT PLANS FOR THESE SAME JOBS BEFORE | | | SUBMITTING FOR PERMIT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|