| Plan Review Notes For Permit 07020065 |
| Permit Number |
07020065 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-09 07:25:10 | | | | | | | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT | | | SATISFY THIS REQUIREMENT. | | | | | | 2} THE REFERENCE TO THE 2002NEC IS ALSO INCORRECT IN | | | THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA | | | LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION | | | FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE | | | SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO | | | REFLECT THIS CHANGE. | | | | | | 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE | | | ENTRANCE CONDUCTORS ROUTE TO THE MAIN BRAKER. IF THEY | | | ROUTE OVERHEAD THROUGH THE GARAGE, THEN A MAIN | | | DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1). | | | IF THEY ARE UNDER THE SLAB THE MAIN IN THE PANEL WOULD | | | BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE DISCONNECT IF | | | NECESSARY. | | | | | | 4} A RECEPTACLE IS REQUIRED IN THE 2ND FLOOR HALL PER | | | 21052(E). | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561) 805-6718 |
|