| 2007-05-01 10:00:55 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 2) ENERGY CALCULATIONS, CONSERVATION CREDITS SHOW |
| | DEDICATED HEAT PUMP BEING INSTALLED, ELECTRICAL PLANS |
| | SHOW AN ELECTRIC HEATER BEING INSTALLED, MECHANICAL |
| | PLANS SHOW NO HEAT BEING INSTALLED, PLEASE CORRECT SO |
| | ALL THREE ARE THE SAME. |
| | |
| | 3) MECHANICAL PLANS EQUIPMENT LISTING NEED CONDENSER |
| | UNIT MODEL NUMBER, ELECTRIC HEATER KW, IF HEAT PUMP |
| | UNIT PLEASE STATE SO ON PLANS SO SEER MAY BE VERIFIED |
| | WITH THE ARI DIRECTORY. |
| | |
| | 4) SEE MECHANICAL PLANS SHOW THE MASTER BATHROOM |
| | EXHAUST FAN OUTSIDE OF THE WATER CLOSET ROOM, IF TWO |
| | ARE BEING INSTALLED ADD ONE TO WATER CLOSET ROOM, IF |
| | NOT MOVE TO WATER CLOSET ROOM. |
| | |
| | 5) SUPPLY AIR DUCT (FLEX) TO MIXING BOX FIRST FLOOR |
| | FAMILY ROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT ON |
| | MECHANICAL PLANS. |
| | |
| | 6) 12" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS |
| | TO BE 16", SEE 2004 FBC/R M1602.4 (A) AND (C) EXCEPT. |
| | PLEASE CORRECT. |
| | |
| | ** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |