| Date |
Text |
| 2007-03-23 14:10:03 | BUILDING REVIEWCHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC 713.13 |
| | FLORIDA STATUTES. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES. |
| | BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT. |
| | ***NOTE: MAKE SURE CORRECT BUILDING AREA IS SHOWN ON |
| | PLANS. |
| | |
| | 3- SHEET A-1.0: |
| | A) REVISE TYPE OF CONSTRUCTION. SEE SEC. 602 FBC |
| | 2004. TYPE OF CONSTRUCTION SHOWN ON PLANS APPLIES TO |
| | TYPE IIIB. |
| | B) ADD 2004 FLORIDA RESIDENTIAL CODE, WHICH IS THE |
| | ONE THAT APPLIES TO SINGLE FAMILY RESIDENCES. |
| | C) AREA CALCULATIONS ON SHEET A-1.0 ARE DIFFERENT |
| | THAN THOSE SHOWN ON SHEET A-1.1. REVISE AS REQUIRED. |
| | |
| | 4- ENERGY CALCULATIONS: |
| | A) REVISE OVERHANG LENGTH AND HEIGHT. SEE PLANS. |
| | |
| | B) MAKE SURE A/C AREA MATCHES PLANS. |
| | C) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| | PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION |
| | SCHEDULE. |
| | |
| | *** NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE IN |
| | WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- BUILDING VALUATION AND RADON FEES WILL BE UPDATED |
| | WHEN CORRECT FLOOR AREAS ARE PROVIDED. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | *** NOTE: PLEASE MAKE SURE DRAWINGS ARE LEGIBLE. |
| | B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON |
| | PLANS. |
| | *** NOTE: SEE SIZE OF DOORS SPECIFIED ON PLANS. |
| | C) DOUBLE GARAGE DOOR AS SHOWN ON EXTERIOR |
| | ELEVATION. |
| | D) ASPHALT SHINGLES.NOA #04-0305.03 EXPIRED ON |
| | 02/21/07. |
| | E) SINGLE HUNG WINDOWS. NEED LEGIBLE DRAWINGS. F) |
| | COLONIAL SHUTTERS SHOWN ON EXTERIOR ELEVATIONS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S |
| | REGISTRATION NUMBERAS REQUIRED BY SEC. 61G1-16.004 OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 10- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 472 FLORIDA STATUTES. |
| | |
| | 11- SHEET A-2.1: |
| | A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR. |
| | ELEVATION SHOWS 2 SMALL GARAGE DOORS. CLARIFY/REVISE AS |
| | REQUIRED TO MATCH. |
| | B) REVISE ELEVATIONS CARDINAL ORIENTATION. SEE |
| | SURVEY FOR CORRECT ORIENTATION. |
| | |
| | 12- SHEET A-3.1:A) PORCH SECTION AND TYPICAL WALL |
| | SECTION CALL FOR "ASPHALT TILE ROOF". CLARIFY WHAT IS |
| | IT?. REVISE AS REQUIRED. |
| | |
| | B) SPECIFY FASTENERS FOR 2X4 FRAMED DOWN CEILING AT |
| | ENTRY PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 13- SHEET A-4.1: |
| | A) DETAIL #1 IS FOR WINDOW AND DOOR BUCK DETAIL. |
| | CLARIFY TITLE SAYS WINDOW, WHILE DETAIL SAYS DOOR |
| | FRAME. |
| | B) THERE ARE TWO DIFFERENT SPECS FOR BUCK FASTENING. |
| | SEE DETAIL 1 AND WINDOW/DOOR BUCK NOTES ON SHEET S-2 |
| | AND REVISE AS REQUIRED. |
| | C) HURRICANE PANEL DETAIL: EDGE DISTANCE IS |
| | INCORRECT. STUCCO THICKNESS CAN'T BE CONSIDERED FOR |
| | EDGE DISTANCE. REVISE AS REQUIRED. SEE ACTUAL STORM |
| | PANELS PRODUCT APPROVAL. |
| | ***NOTE: THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND |
| | WILL AVOID DISCREPANCIES IF ONLY THE PRODUCT APPROVAL |
| | FOR STORM SHUTTERS IS PROVIDEDANDAPPROVED BY THE |
| | DESIGNER OF RECORD. |
| | D) SECTION AT REAR PORCH: SPECIFY LEDGERS FOR ROOF |
| | SHEATHING SUPPORT AT MASONRY WALL. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | ALSO,SPECIFY FIREBLOCKING. SEC. R602.8 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 14- SHEET S-2:DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, |
| | WHILE 2ND FLOOR FRAMING PLAN CALLS FOR (4)2X4 STUDS. |
| | CLARIFY/REVISE AS REQUIRED TO MATCH. |
| | |
| | |
| | 15- SHEET S-3: |
| | A) REVISE PLYWOOD SHEATHING NAILING SPECIFICATIONS |
| | FOR ROOF SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | B) SPECIFICATION GIVENON PLYWOOD SHEATHING NAILING |
| | SCHEDULE AND OVERHANG DETAIL DON'T MATCH. REVISE AS |
| | REQUIRED. |
| | C) CONNECTOR SCHEDULE: REVISE UPLIFT AND FASTENERS |
| | SPECIFIED FOR SIMPSON HETAL 16 AND SP4. SEE CURRENT |
| | CATALOG AND UPDATE AS REQUIRED. OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS FOR VALUES AND NUMBERS |
| | THAT ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY |
| | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | D) MAXIMUM DESIGN PRESSURES SHOWN ARE LOW COMPARED |
| | TO TABLE R301.2((2) OF 2004 FLORIDA RESIDENTIALCODE |
| | OR TABLES IN ASCE 7-02.PROVIDE ACTUAL CALCULATIONS |
| | SHOWING HOW THE MAXIMUM POSITIVE AND NEGATIVE LOADS ARE |
| | DETERMINED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- SOIL TEST REPORT TO HAVE ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS |
| | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |