| Date |
Text |
| 2007-02-08 12:16:22 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT |
| | SATISFY THIS REQUIREMENT. |
| | |
| | 2} THE REFERENCE TO THE 2002NEC IS ALSO INCORRECT IN |
| | THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA |
| | LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION |
| | FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE |
| | SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO |
| | REFLECT THIS CHANGE. |
| | |
| | 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE |
| | ENTRANCE CONDUCTORS ROUTE TO THE MAIN BREAKER. IF THEY |
| | ROUTE OVERHEAD THROUGH THE RESIDENCE, THEN A MAIN |
| | DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1). |
| | IF THEY ARE UNDER THE BUILDING THE MAIN IN THE PANEL |
| | WOULD BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE |
| | DISCONNECT IF NECESSARY. |
| | |
| | 4} THE NOTE AT THE RISER INDICATING A DETACHED GARAGE |
| | WOULD MAKE IT NECESSARY TO SHOW THAT FEED ON THE RISER |
| | AND INDICATE WHERE THE OCP IS LOCATED. IF FED FROM THE |
| | PANEL ADD TO THE SCHEDULWE. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | 561) 805-6718 |