| 2007-07-04 09:54:54 | 2007-07-04 09:54:54 |
| | |
| | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS. |
| | PLEASE SEE THE ENERGY CALCULATION AS SUBMITTED UNDER |
| | PERMIT APPLICATION WERE THE INCORRECT VERSION. PLEASE |
| | SEE THE VERSION SUBMITTED WAS 2.1 WHICH WAS IN EFFECT |
| | ON THE PREVIOUS REVISIONS TO THE FBC AND NOT IN EFFECT |
| | AFTER DECEMBER 8TH, 2006. PLEASE SEE THE REVISED ENERGY |
| | CALCULATIONS ARE NEEDED AS LIGHTING HAS BEEN REVISED. |
| | 13-415.1.C, 13-415.2 |
| | |
| | 2) NOTE: PLEASE CLARIFY THE FOLLOWING ROOMS AS THESE |
| | ARE NOTED ON PLANS AS EXISTING HOWEVER THE LIGHTING |
| | APPEARS TO BE SHOWN BEING REPLACED? PLEASE SEE OTHER |
| | ROOMS WHICH ARE EXISTING INDICATE LIGHTING AS *LT GRAY* |
| | AND DASHED LINES. PLEASE KNOW ANY OF THESE FOLLOWING |
| | ROOMS WHICH LIGHTING FIXTURES ARE BEING REPLACED OR |
| | CONTROL DEVICES ARE BEING CHANGED/REPLACE OR RELOCATED |
| | WILL BE REQUIRED TO MEET THE FBC CHAPTER 13 AS OTHER |
| | ROOMS ARE DONE. |
| | PLEASE SEE THE ROOMS ARE AS NOTED: |
| | LAB E, GUEST LOUNGE, OFFICES 131-137. 13-415.1.1,.1.2, |
| | 13-101 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |