Plan Review Notes
Plan Review Notes For Permit 07020042
Permit Number 07020042
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-04 09:54:542007-07-04 09:54:54
  
 ** UNSAT **
  
  
 1) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS.
 PLEASE SEE THE ENERGY CALCULATION AS SUBMITTED UNDER
 PERMIT APPLICATION WERE THE INCORRECT VERSION. PLEASE
 SEE THE VERSION SUBMITTED WAS 2.1 WHICH WAS IN EFFECT
 ON THE PREVIOUS REVISIONS TO THE FBC AND NOT IN EFFECT
 AFTER DECEMBER 8TH, 2006. PLEASE SEE THE REVISED ENERGY
 CALCULATIONS ARE NEEDED AS LIGHTING HAS BEEN REVISED.
 13-415.1.C, 13-415.2
  
 2) NOTE: PLEASE CLARIFY THE FOLLOWING ROOMS AS THESE
 ARE NOTED ON PLANS AS EXISTING HOWEVER THE LIGHTING
 APPEARS TO BE SHOWN BEING REPLACED? PLEASE SEE OTHER
 ROOMS WHICH ARE EXISTING INDICATE LIGHTING AS *LT GRAY*
 AND DASHED LINES. PLEASE KNOW ANY OF THESE FOLLOWING
 ROOMS WHICH LIGHTING FIXTURES ARE BEING REPLACED OR
 CONTROL DEVICES ARE BEING CHANGED/REPLACE OR RELOCATED
 WILL BE REQUIRED TO MEET THE FBC CHAPTER 13 AS OTHER
 ROOMS ARE DONE.
 PLEASE SEE THE ROOMS ARE AS NOTED:
 LAB E, GUEST LOUNGE, OFFICES 131-137. 13-415.1.1,.1.2,
 13-101
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-04 09:01:072007-07-04 09:01:07
 PLANS REMOVED FROM INCOMING, WILL RETURN TO INCOMING
 ONCE ELECTRICAL REVIEW IS DONE.