2007-08-16 17:37:12BUILDING PLAN REVIEW
 PERMIT: 07020042
 ADD: 1400 NORTHPOINT PARKWAY
 CONT: BRICAR ENTERPRISES, INC
 TEL: (954)675-1976
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW REVISION # 4
 ACTION: DENIED
  
 1) SHEET A4 DETAIL P2 & P3 DOES NOT INDICATE HOW THE
 TOP OF THE WALL WILL BE ANCHORED. IT CURRENTLY IS
 FLOATING WITH NO LATERAL BRACING.
 WHAT TYPE OF MATERIALS WILL BE USED IN THIS LAB, IS IT
 TO BE CONSIDERED A CONTROLED AREA ?IF SO:414.2.3
 SEPARATION.
 THE REQUIRED FIRE-RESISTANCE RATING FOR FIRE BARRIER
 ASSEMBLIES SHALL BE IN ACCORDANCE WITH TABLE 414.2.2 .
 THE FLOOR CONSTRUCTION OF THE CONTROL AREA , AND THE
 CONSTRUCTION SUPPORTING THE FLOOR OF THE CONTROL AREA ,
 SHALL HAVE A MINIMUM 2-HOUR FIRE-RESISTANCE RATING.
  
 2) PLEASE PROVIDE THE CRITERIA TO DETERMINE THE 5 LBS.
 PER SQ FT FOR BOTH STRESS AND DEFLECTION REQUIREMENTS,
 WHAT ARE THE DEFLECTION LIMITS?
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]