| Plan Review Notes For Permit 07020042 |
| Permit Number |
07020042 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-08-16 17:37:12 | BUILDING PLAN REVIEW | | | PERMIT: 07020042 | | | ADD: 1400 NORTHPOINT PARKWAY | | | CONT: BRICAR ENTERPRISES, INC | | | TEL: (954)675-1976 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW REVISION # 4 | | | ACTION: DENIED | | | | | | 1) SHEET A4 DETAIL P2 & P3 DOES NOT INDICATE HOW THE | | | TOP OF THE WALL WILL BE ANCHORED. IT CURRENTLY IS | | | FLOATING WITH NO LATERAL BRACING. | | | WHAT TYPE OF MATERIALS WILL BE USED IN THIS LAB, IS IT | | | TO BE CONSIDERED A CONTROLED AREA ?IF SO:414.2.3 | | | SEPARATION. | | | THE REQUIRED FIRE-RESISTANCE RATING FOR FIRE BARRIER | | | ASSEMBLIES SHALL BE IN ACCORDANCE WITH TABLE 414.2.2 . | | | THE FLOOR CONSTRUCTION OF THE CONTROL AREA , AND THE | | | CONSTRUCTION SUPPORTING THE FLOOR OF THE CONTROL AREA , | | | SHALL HAVE A MINIMUM 2-HOUR FIRE-RESISTANCE RATING. | | | | | | 2) PLEASE PROVIDE THE CRITERIA TO DETERMINE THE 5 LBS. | | | PER SQ FT FOR BOTH STRESS AND DEFLECTION REQUIREMENTS, | | | WHAT ARE THE DEFLECTION LIMITS? | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|