| Plan Review Notes For Permit 07020042 |
| Permit Number |
07020042 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-20 11:37:40 | *****DENIED***** | | | | | | | | | 1.PLEASE EXPLAIN THE DISCREPANCY ON SHEET LS 1 | | | (EXISTING CHILLER COMPOUND) COMPARED TO SHEET A 1 | | | (EXISTING COVERED PATIO) AREA.IF THIS AREA IS INDEED | | | REFERENCED AS AN EXISTING CHILLER COMPOUND AREA, | | | EXPLAIN WHAT THIS AREA IS AND ENTAILS.PLEASE BE | | | ADVISED THAT IF THIS AREA IS IDENTIFIED AS MORE | | | HAZARDOUS, EXITING OR EXIT ACCESS SHALL NOT BE THROUGH | | | SUCH ROOMS OR SPACES. | | | | | | 2.THE INTERIOR WALL AND CEILING FINISH MATERIALS | | | SHALL BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS | | | CORRIDORS, AND SHALL BE CLASS A, CLASS B, OR CLASS C IN | | | ALL OTHER SPACES.PLEASE SPECIFY. | | | | | | 3.IT IS STATED THAT THIS SPACE IS FULLY SPRINKLERED, | | | WILL THE LOCATION OF FIRE SPRINKLER HEADS/DEVICES BE | | | MODIFIED DUE TO THE SCOPE OF WORK?IF SO,SEPARATE | | | PERMIT AND PLANS WILL BE REQUIRED FOR THE FIRE | | | SPRINKLER REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|