Plan Review Notes
Plan Review Notes For Permit 07020042
Permit Number 07020042
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-13 12:19:11*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THE CODE WHICH SHOULD BE STATED ON
 PLANS ARE THE 2005 NFPA-70 AND THE 2004 FBC 2006
 REVISIONS.
 PLEASE SEE THE OTHER CODES REFLECTED ON ELECTRICAL
 PLANS ARE OK AND CURRENT.
  
 ** ALL PERMIT APPLICATIONS WHICH ARE APPLIED FOR AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE NEW CODES.
  
 2) NOTE: PLEASE SEE THE EGRESS PATH ON THE LIFE SAFETY
 PLAN DOES NOT CORRELATE WITH THE ELECTRICAL PLANS AND
 ARCHITECTURAL SHEETS FOR THE LAYOUT OF FURNITURE ETC.
 PLEASE SEE BUILDING AND FIRE REVIEW COMMENTS AS THIS
 MAY DIRECTLY AFFECT THE EGRESS PATHS AND ELECTRICAL
 LAYOUTS FOR EQUIPMENT/CUBICLES ETC
 LS 101
  
 3) NOTE: PLEASE CLARIFY USE AND OCCUPANCY AS THE PLANS
 MENTIONS "LAB", HOWEVER WHAT TYPE OF LAB WORK IS BEING
 DONE, WHAT TYPE PF MATERIALS ETC.
 PLEASE SEE NEC 500.
 REVIEW FOR USE AND ELECTRICAL CAN NOT BE VERIFIED AT
 THIS TIME.
  
 4) NOTE: PLEASE CLARIFY NOTE WHICH MENTIONS THE ENTIRE
 SPACE IS GOING TO HAVE CONTROLS IN FOR CHAPTER 13
 REQUIREMENTS HOWEVER THE PLANS DO NOT CORRELATE WITH
 THE ENTIRE SPACE?
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE SOME AREAS WHICH WALL SWITCH TYPE
 OCCUPANCY DEVICES ARE BEING INDICATED FOR HALL AND
 LARGER OPEN AREAS, HOWEVER THE WALL DEVICE DOES NOT
 SEEM IT WILL PROVIDE THE COVERAGE AS NEEDED FOR
 LIGHTING CONTROL FOR THE OCCUPANTS. PLEASE SEE THE
 POSSIBILITY OF CEILING MOUNTED DEVICES IN HALLS AND
 LARGER AREAS. (WALLS AND OTHER OBSTRUCTIONS WILL
 INTERFERE WITH WALL DEVICES).
 PLEASE SEE HALLS ALSO.
  
 *PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS FOR
 NEW FIXTURES AND LPD AS STATED IN 13-415.2.
  
 5) NOTE: PLEASE SEE RISER SHOWS PANEL TSC AND EPA,
 HOWEVER THESE WERE NOT SUBMITTED. PLEASE CLARIFY.
 408.4, 310.16, 240.4.
 FBC 106.1.2 ADMIN SECTION.
  
  
 6) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL
 CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL
 CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE
 SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER
 LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD
 CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL
 NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT
 200%.
 PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO
 PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE
 CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN
 AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS
 MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH
 INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE
 CONDUCTOR OR CIRCUIT AND FEEDERS.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH
 DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN),310.10,
 310.15B4(C), 400.5, 520.44, 408.16.
 PLEASE SEE NFPA-70B, ANSI/IEEE 519 AND FBC 104.6
 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
 PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE
 TAKEN TO ALLEVIATE THESE RISKS.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]