| Date |
Text |
| 2007-02-13 12:19:11 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE CODE WHICH SHOULD BE STATED ON |
| | PLANS ARE THE 2005 NFPA-70 AND THE 2004 FBC 2006 |
| | REVISIONS. |
| | PLEASE SEE THE OTHER CODES REFLECTED ON ELECTRICAL |
| | PLANS ARE OK AND CURRENT. |
| | |
| | ** ALL PERMIT APPLICATIONS WHICH ARE APPLIED FOR AFTER |
| | DECEMBER 8TH, 2006 FALL UNDER THE NEW CODES. |
| | |
| | 2) NOTE: PLEASE SEE THE EGRESS PATH ON THE LIFE SAFETY |
| | PLAN DOES NOT CORRELATE WITH THE ELECTRICAL PLANS AND |
| | ARCHITECTURAL SHEETS FOR THE LAYOUT OF FURNITURE ETC. |
| | PLEASE SEE BUILDING AND FIRE REVIEW COMMENTS AS THIS |
| | MAY DIRECTLY AFFECT THE EGRESS PATHS AND ELECTRICAL |
| | LAYOUTS FOR EQUIPMENT/CUBICLES ETC |
| | LS 101 |
| | |
| | 3) NOTE: PLEASE CLARIFY USE AND OCCUPANCY AS THE PLANS |
| | MENTIONS "LAB", HOWEVER WHAT TYPE OF LAB WORK IS BEING |
| | DONE, WHAT TYPE PF MATERIALS ETC. |
| | PLEASE SEE NEC 500. |
| | REVIEW FOR USE AND ELECTRICAL CAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | |
| | 4) NOTE: PLEASE CLARIFY NOTE WHICH MENTIONS THE ENTIRE |
| | SPACE IS GOING TO HAVE CONTROLS IN FOR CHAPTER 13 |
| | REQUIREMENTS HOWEVER THE PLANS DO NOT CORRELATE WITH |
| | THE ENTIRE SPACE? |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THERE ARE SOME AREAS WHICH WALL SWITCH TYPE |
| | OCCUPANCY DEVICES ARE BEING INDICATED FOR HALL AND |
| | LARGER OPEN AREAS, HOWEVER THE WALL DEVICE DOES NOT |
| | SEEM IT WILL PROVIDE THE COVERAGE AS NEEDED FOR |
| | LIGHTING CONTROL FOR THE OCCUPANTS. PLEASE SEE THE |
| | POSSIBILITY OF CEILING MOUNTED DEVICES IN HALLS AND |
| | LARGER AREAS. (WALLS AND OTHER OBSTRUCTIONS WILL |
| | INTERFERE WITH WALL DEVICES). |
| | PLEASE SEE HALLS ALSO. |
| | |
| | *PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS FOR |
| | NEW FIXTURES AND LPD AS STATED IN 13-415.2. |
| | |
| | 5) NOTE: PLEASE SEE RISER SHOWS PANEL TSC AND EPA, |
| | HOWEVER THESE WERE NOT SUBMITTED. PLEASE CLARIFY. |
| | 408.4, 310.16, 240.4. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | |
| | 6) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL |
| | CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL |
| | CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE |
| | SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER |
| | LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH |
| | PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR |
| | LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY |
| | METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD |
| | CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL |
| | NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT |
| | 200%. |
| | PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO |
| | PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE |
| | CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN |
| | AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS |
| | MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH |
| | INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE |
| | CONDUCTOR OR CIRCUIT AND FEEDERS. |
| | PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF |
| | WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH |
| | DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN),310.10, |
| | 310.15B4(C), 400.5, 520.44, 408.16. |
| | PLEASE SEE NFPA-70B, ANSI/IEEE 519 AND FBC 104.6 |
| | ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST |
| | PALM BEACH. |
| | PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE |
| | TAKEN TO ALLEVIATE THESE RISKS. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |