2007-03-09 16:58:51BUILDING PLAN REVIEW
 PERMIT: 07020042
 ADD: 1400 NORTHPOINT PRKY# 10
 CONT: FISHER CONSTRUCTION
 TEL: (561758-6545
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) 106.1.2*ADDITIONAL INFORMATION REQUIRED, THE PLANS
 INDICATE ROOMS 106 & 110 TO BE ELECTRICAL ROOMS? IS
 THERE ANY GAS CYLINDERS IN EITHER OF TTHESE ROOMS? IF
 SO WHAT TYPE OF GASSES ARE THERE AND IN WHAT SIZE
 CYLINDERS, POUNDS OR GALLONS?
 THIS SITE WAS PERMITTED WITH THESE ROOMS BEING
 EXPLOSION PROOF ROOMS WITH BLOW OUT PANELS THROUGH THE
 ROOF AS WELL AS THE WALLS AND DOORS BECAUSE OF THE
 HYDROGEN
 CYLINDERS BEING HOUSED IN THESE ROOMS. THERE WAS ALSO A
 KNOX BOX INCORPORATED INTO THE SITE WITH MSDS SHEETS AS
 TO THE CHEMICALS BEING STORED AND THE QUANITIES. THIS
 SITE WAAS CONSIDERED A BUSINESS OCCUPANCY WITH CONTROL
 AREAS, ARE ANY OF THE LABS ADDING EQUIPMENT REQUIRING
 PIPING, AND OR VENTILATION?
  
 4)ROOMS 116, 117B & 119B PLEASE SEE ACCESSIBLE
 DOORS,
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 5) DISCREPANCY BETWEEN LS-1 AND A1 IN THE AREA OF
 COVERED PATIO VS BEING AN AREADESIGNATED AS A CHILLER
 COMPOUND? LS PLAN INDICATES 2 MEANS OF EGRESS TRAVELING
 THROUGH THE
 CHILLER COMPOUND, IF THIS IS SUCH AN AREA WOULDN'T THE
 GATES BE LOCKED , FOR AUTHORIZED PERSONEL ONLY?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  