| 2007-03-09 16:58:51 | BUILDING PLAN REVIEW |
| | PERMIT: 07020042 |
| | ADD: 1400 NORTHPOINT PRKY# 10 |
| | CONT: FISHER CONSTRUCTION |
| | TEL: (561758-6545 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) 106.1.2*ADDITIONAL INFORMATION REQUIRED, THE PLANS |
| | INDICATE ROOMS 106 & 110 TO BE ELECTRICAL ROOMS? IS |
| | THERE ANY GAS CYLINDERS IN EITHER OF TTHESE ROOMS? IF |
| | SO WHAT TYPE OF GASSES ARE THERE AND IN WHAT SIZE |
| | CYLINDERS, POUNDS OR GALLONS? |
| | THIS SITE WAS PERMITTED WITH THESE ROOMS BEING |
| | EXPLOSION PROOF ROOMS WITH BLOW OUT PANELS THROUGH THE |
| | ROOF AS WELL AS THE WALLS AND DOORS BECAUSE OF THE |
| | HYDROGEN |
| | CYLINDERS BEING HOUSED IN THESE ROOMS. THERE WAS ALSO A |
| | KNOX BOX INCORPORATED INTO THE SITE WITH MSDS SHEETS AS |
| | TO THE CHEMICALS BEING STORED AND THE QUANITIES. THIS |
| | SITE WAAS CONSIDERED A BUSINESS OCCUPANCY WITH CONTROL |
| | AREAS, ARE ANY OF THE LABS ADDING EQUIPMENT REQUIRING |
| | PIPING, AND OR VENTILATION? |
| | |
| | 4)ROOMS 116, 117B & 119B PLEASE SEE ACCESSIBLE |
| | DOORS, |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 5) DISCREPANCY BETWEEN LS-1 AND A1 IN THE AREA OF |
| | COVERED PATIO VS BEING AN AREADESIGNATED AS A CHILLER |
| | COMPOUND? LS PLAN INDICATES 2 MEANS OF EGRESS TRAVELING |
| | THROUGH THE |
| | CHILLER COMPOUND, IF THIS IS SUCH AN AREA WOULDN'T THE |
| | GATES BE LOCKED , FOR AUTHORIZED PERSONEL ONLY? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |