Plan Review Notes
Plan Review Notes For Permit 07020013
Permit Number 07020013
Review Stop B
Sequence Number 2
Notes
Date Text
2007-05-30 10:02:53BUILDING PLAN REVIEW
 PERMIT: 07020013
 ADD: 1301 SUMMIT BLVD.
 CONT: RIDDLE CONSTRUCTION
 TEL: (561)616-9179
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)2ND REQUEST,COMMENT (4C) FROM THE PREVIOUS REVIEW,
 TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, TABLE 503
 & 601.
 SHEET AR03 INDICATES THIS IS A TYPE IV CONSTRUCTION,
 HEAVY TIMBER, THIS STRUCTURE DOES NOT QUALIFY
 AS HEAVY CONSTRUCTION DUE TO THE FAFTERS AND ROOF DECK
 NOT MEETING THE REQUIREMEENTS OF HEAVY TIMBER
 CONSTRUCTION, PLEASE SEE SECTION 602.4.3 ROOF FRAMING &
 602.4.5 FOR ROOF DECKING.
  
 3) 2ND REQUEST, COMMENT (5B) FROM THE PREVIOUS REVIEW,
 PLEASE PROVIDE ORIGINALS (2) OF THE SOILS REPORTTHAT
 WAS COMPLETED BY DUNKELBURGER TESTING. FBC 1802.2.1
 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) 2ND REQUEST, COMMENT (6) FROM THE PREVIOUS REVIEW,
  
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: STRUCTURAL COMPONENTS
 A) TRUSS STRAPS
 B) WOOD CONNECTORS
 C) ANCHORS
 THE CODE SECTION ACTUALLY INDICATES THE TESTING
 REPORT FOR EACH COMPONENT IS TO BE SUBMITTED!!!!!!
  
 5) 2ND REQUEST, COMMENT NUMBER (7) FROM THE PREVIOUS
 REVIEW.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) 2ND REQUEST, COMMENTNUMBER (8) FROM THE PREVIOUS
 REVIEW,
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 NOTE: PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  