| 2007-05-30 10:02:53 | BUILDING PLAN REVIEW |
| | PERMIT: 07020013 |
| | ADD: 1301 SUMMIT BLVD. |
| | CONT: RIDDLE CONSTRUCTION |
| | TEL: (561)616-9179 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)2ND REQUEST,COMMENT (4C) FROM THE PREVIOUS REVIEW, |
| | TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, TABLE 503 |
| | & 601. |
| | SHEET AR03 INDICATES THIS IS A TYPE IV CONSTRUCTION, |
| | HEAVY TIMBER, THIS STRUCTURE DOES NOT QUALIFY |
| | AS HEAVY CONSTRUCTION DUE TO THE FAFTERS AND ROOF DECK |
| | NOT MEETING THE REQUIREMEENTS OF HEAVY TIMBER |
| | CONSTRUCTION, PLEASE SEE SECTION 602.4.3 ROOF FRAMING & |
| | 602.4.5 FOR ROOF DECKING. |
| | |
| | 3) 2ND REQUEST, COMMENT (5B) FROM THE PREVIOUS REVIEW, |
| | PLEASE PROVIDE ORIGINALS (2) OF THE SOILS REPORTTHAT |
| | WAS COMPLETED BY DUNKELBURGER TESTING. FBC 1802.2.1 |
| | QUESTIONABLE SOILS, |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 4) 2ND REQUEST, COMMENT (6) FROM THE PREVIOUS REVIEW, |
| | |
| | FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: STRUCTURAL COMPONENTS |
| | A) TRUSS STRAPS |
| | B) WOOD CONNECTORS |
| | C) ANCHORS |
| | THE CODE SECTION ACTUALLY INDICATES THE TESTING |
| | REPORT FOR EACH COMPONENT IS TO BE SUBMITTED!!!!!! |
| | |
| | 5) 2ND REQUEST, COMMENT NUMBER (7) FROM THE PREVIOUS |
| | REVIEW. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6) 2ND REQUEST, COMMENTNUMBER (8) FROM THE PREVIOUS |
| | REVIEW, |
| | WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | NOTE: PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| | AN ADDITIONAL 6". |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |