2007-10-19 09:16:08REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 1. THE SUBMITTED GAS REVISION CAN NOT BE PASSED DUE TO
 THE REFERENCED MASTER PERMIT #05061664 PLANS DO NOT
 HAVE AN APPROVED LOCATION BY ZONING FOR THE GENERATOR
 LOCATION OR APPROVAL FOR THE GENERATOR BEING ANCHORED
 TO MEET 140-MPH WIND LOAD PER FBC-2004 W/ 06 REV.
 SECTION 1603.1.4, WIND DESIGN DATA AND SECTION
 1609.1.3, ANCHORAGE AGAINST OVERTURNING, UPLIFT, AND
 SLIDING. EITHER A REVISION IS REQUIRED FOR THE MASTER
 PERMIT #05061664 WITH THIS INFORMATION OR A SEPERATE
 GEN/RES PERMIT IS REQUIRED WITH ALL THE REQUIRED
 INFORMATION FOR A GENERATOR PERMIT.
 NOTE: THE APPROVED MASTER PERMIT DOES HAVE THE
 MANUFACTURER SPECIFICATIONS FOR THE ATS AND GENERATOR
 AND DOES SHOW THIS GENERATOR INFORMATION ON THE
 ELECTRICAL RISER.
  