| Plan Review Notes For Permit 07011374 |
| Permit Number |
07011374 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-19 09:16:08 | REVISION DENIED | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | 1. THE SUBMITTED GAS REVISION CAN NOT BE PASSED DUE TO | | | THE REFERENCED MASTER PERMIT #05061664 PLANS DO NOT | | | HAVE AN APPROVED LOCATION BY ZONING FOR THE GENERATOR | | | LOCATION OR APPROVAL FOR THE GENERATOR BEING ANCHORED | | | TO MEET 140-MPH WIND LOAD PER FBC-2004 W/ 06 REV. | | | SECTION 1603.1.4, WIND DESIGN DATA AND SECTION | | | 1609.1.3, ANCHORAGE AGAINST OVERTURNING, UPLIFT, AND | | | SLIDING. EITHER A REVISION IS REQUIRED FOR THE MASTER | | | PERMIT #05061664 WITH THIS INFORMATION OR A SEPERATE | | | GEN/RES PERMIT IS REQUIRED WITH ALL THE REQUIRED | | | INFORMATION FOR A GENERATOR PERMIT. | | | NOTE: THE APPROVED MASTER PERMIT DOES HAVE THE | | | MANUFACTURER SPECIFICATIONS FOR THE ATS AND GENERATOR | | | AND DOES SHOW THIS GENERATOR INFORMATION ON THE | | | ELECTRICAL RISER. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|