Plan Review Notes
Plan Review Notes For Permit 07011368
Permit Number 07011368
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-20 16:49:19 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE CIRCUIT NUMBER AT THE DEVICES ARE NOT REQUIRED
 FOR A RESIDENTIAL PLAN. IF THEY ARE PROVIDED THEY MUST
 CORRELATE WITH THE PANEL SCHEDULE.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, ANDPANEL SCHEDULE
 FOR THE NEW 100 AMP PANEL SHOWN.
  
 3} RECEPTACLES MUST BE ADDED TO THE NEW ROOM PER
 210.52(B), SEE REVIEWED SET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.