| Plan Review Notes For Permit 07011368 |
| Permit Number |
07011368 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-20 16:49:19 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE CIRCUIT NUMBER AT THE DEVICES ARE NOT REQUIRED | | | FOR A RESIDENTIAL PLAN. IF THEY ARE PROVIDED THEY MUST | | | CORRELATE WITH THE PANEL SCHEDULE. | | | | | | 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS, ANDPANEL SCHEDULE | | | FOR THE NEW 100 AMP PANEL SHOWN. | | | | | | 3} RECEPTACLES MUST BE ADDED TO THE NEW ROOM PER | | | 210.52(B), SEE REVIEWED SET. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|