2007-03-16 18:01:32BUILDING REVIEW CHECKLIST:
 1- ARCHITECTURAL PLANS CALL FOR LEVEL 3 RENOVATION. SEE
 CHAPTER 3 OF 2004 EXISTING BUILDING CODE FOR CORRECT
 TYPE OF ALTERATION LEVEL AND REVISE AS REQUIRED.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2 FBC 2004.
 ***NOTE:PLEASE MAKE SURE ALL INFORMATION IS COMPLETE,
 INCLUDING ALL INFORMATION ON TOP OF FORM.AND, FORM IS
 SIGNED BY THE ENERGY CALCULATIONS PREPARER AND THE
 OWNER/AGENT.
  
 3-DRAWINGS NEED TO SPECIFY ROOF INSULATION.
 COORDINATE WITH THE ENERGY CALCULATIONS.
  
 4- PROVIDE CORRECT BUILDING AREA .ACCORDING TO
 DIMENSIONS SHOWN ON PLANS BUILDING AREA IS INCORRECT.
 REVISE AS REQUIRED.UPDATE INFORMATION WITH PALM BEACH
 COUNTY IMPACT FEES DEPARTMENT.
  
 5- VALUATION DECLARED ON THE PERMIT APPLICATION IS TOO
 LOW. PROVIDE UPDATEDVALUATION, INCLUDING ARCHITECT'S
 FEES. OTHERWISEVALUATION WILL BE UPDATED AS REQUIRED
 BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 6- IF USING IMPACT DOORS, THEN CLARIFY WHY SUBMITTING
 PRODUCT APPROVAL FOR STORM SHUTTERS.IF USING SHUTTERS
 PROVIDE COMPLETE INSTALLATION SCHEDULE.SEE ATTACHED
 SAMPLEOF INSTALLATION SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER.
 (561)805-6712