| Plan Review Notes For Permit 07011368 |
| Permit Number |
07011368 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-16 18:01:32 | BUILDING REVIEW CHECKLIST: | | | 1- ARCHITECTURAL PLANS CALL FOR LEVEL 3 RENOVATION. SEE | | | CHAPTER 3 OF 2004 EXISTING BUILDING CODE FOR CORRECT | | | TYPE OF ALTERATION LEVEL AND REVISE AS REQUIRED. | | | | | | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 13-101.2 FBC 2004. | | | ***NOTE:PLEASE MAKE SURE ALL INFORMATION IS COMPLETE, | | | INCLUDING ALL INFORMATION ON TOP OF FORM.AND, FORM IS | | | SIGNED BY THE ENERGY CALCULATIONS PREPARER AND THE | | | OWNER/AGENT. | | | | | | 3-DRAWINGS NEED TO SPECIFY ROOF INSULATION. | | | COORDINATE WITH THE ENERGY CALCULATIONS. | | | | | | 4- PROVIDE CORRECT BUILDING AREA .ACCORDING TO | | | DIMENSIONS SHOWN ON PLANS BUILDING AREA IS INCORRECT. | | | REVISE AS REQUIRED.UPDATE INFORMATION WITH PALM BEACH | | | COUNTY IMPACT FEES DEPARTMENT. | | | | | | 5- VALUATION DECLARED ON THE PERMIT APPLICATION IS TOO | | | LOW. PROVIDE UPDATEDVALUATION, INCLUDING ARCHITECT'S | | | FEES. OTHERWISEVALUATION WILL BE UPDATED AS REQUIRED | | | BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 6- IF USING IMPACT DOORS, THEN CLARIFY WHY SUBMITTING | | | PRODUCT APPROVAL FOR STORM SHUTTERS.IF USING SHUTTERS | | | PROVIDE COMPLETE INSTALLATION SCHEDULE.SEE ATTACHED | | | SAMPLEOF INSTALLATION SCHEDULE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER. | | | (561)805-6712 |
|