| Plan Review Notes For Permit 07011298 |
| Permit Number |
07011298 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-20 07:50:30 | DENIED; | | | 1. PLUMBING NOTES; MINIMUN SLOPE FOR HORIZONTAL PIPE 2 | | | 1/2" AND SMALLER IS 1/4" PER FOOT. FBC-2004 PLUMBING | | | TABLE 704.1. | | | 2. A SANITARY RISER DIAGRAM IS REQUIRED. FBC-2004 | | | BUILDING CHAPTER 1 SECTION 106.3.5.4 (9). SIZE ALL | | | DRAIN AND VENT PIPES. SHOW SEWER TIE-IN LOCATIONS. THE | | | DRAIN PIPE FOR THE AUTOMATIC CLOTHES WASHER IS REQUIRED | | | TO BE 3" WITH A CLEANOUT AT 48" OFF FINISH FLOOR. | | | SECTION 406.3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|