Plan Review Notes
Plan Review Notes For Permit 07011298
Permit Number 07011298
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-15 11:58:23*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) NEED TO SUBMIT TWO (2) COPY'S OF THE ENERGY
 CALCULATIONS AND ALL PLANS.
  
 3) THE MECHANICAL PLANS NEED KEEP IT COOL INC. LICENSE
 NUMBER, PHONE NO., AND ADDRESS IN THE TITLE BLOCK.
  
 5) THE MECHANICAL PLANS NEED TO BE SIGNED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1 .
  
 6) PLEASE SHOW ON THE MECHANICAL PLANS ANY BATHROOM
 EXHAUST FANS BEING INSTALLED, THE WATER CLOSET IN THE
 MASTER BATH MUST HAVE AN EXHAUST FAN, PER 2004 FBC/R
 303.3.
  
 7) THE 9" RETURN AIR TRANSFER DUCT IN THE MASTER SUITE
 NEEDS TO BE 12", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT.
  
 8) THE 8" RETURN AIR TRANSFER DUCT IN BEDROOM #2 NEEDS
 TO BE 9", SEE 2004 FBC/R M1602.4 (A).
  
 9) THE 7" RETURN AIR TRANSFER DUCT IN BEDROOM #3 NEEDS
 TO BE 9", SEE 2004 FBC/R M1602.4 (A).
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.