| 2007-02-15 11:58:23 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 2) NEED TO SUBMIT TWO (2) COPY'S OF THE ENERGY |
| | CALCULATIONS AND ALL PLANS. |
| | |
| | 3) THE MECHANICAL PLANS NEED KEEP IT COOL INC. LICENSE |
| | NUMBER, PHONE NO., AND ADDRESS IN THE TITLE BLOCK. |
| | |
| | 5) THE MECHANICAL PLANS NEED TO BE SIGNED. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1 . |
| | |
| | 6) PLEASE SHOW ON THE MECHANICAL PLANS ANY BATHROOM |
| | EXHAUST FANS BEING INSTALLED, THE WATER CLOSET IN THE |
| | MASTER BATH MUST HAVE AN EXHAUST FAN, PER 2004 FBC/R |
| | 303.3. |
| | |
| | 7) THE 9" RETURN AIR TRANSFER DUCT IN THE MASTER SUITE |
| | NEEDS TO BE 12", SEE 2004 FBC/R M1602.4 (A) AND (C) |
| | EXCEPT. |
| | |
| | 8) THE 8" RETURN AIR TRANSFER DUCT IN BEDROOM #2 NEEDS |
| | TO BE 9", SEE 2004 FBC/R M1602.4 (A). |
| | |
| | 9) THE 7" RETURN AIR TRANSFER DUCT IN BEDROOM #3 NEEDS |
| | TO BE 9", SEE 2004 FBC/R M1602.4 (A). |
| | |
| | *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |