Plan Review Notes
Plan Review Notes For Permit 07011298
Permit Number 07011298
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-14 13:21:07 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER
 INFORMATION REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 2} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 3} IF THE SERVICE IS TO BE MOVED OR UPGRADED, TH
 FOLLOWING IS APPLICABLE.
 A) SHOW THE PHYSICAL LOCATION OF ALL SERVICE
 EQUIPMENT ON THE PLAN. 215.5.
 B) PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} ALL RECEPTS SERVING KITCHEN COUNTERSPACE MUST BE
 GFI/GFIPROTECTEDAS REQUIRED PER 210.8(A)(6). INDICATE
 SAME ON PLAN.
  
 5} LIST THE REQ'D ARCFAULT PROTECTED CURCUIT(S) ON
 PANELSCHEDULE. PLEASE SEE THAT ALL "OUTLETS"IN BEDROOMS
 ARE TO BE PROTECTED ,INCLUDING, LTS, RECEPTS, SD'S
 ETC.
  
 6} PROVIDE A LOAD CALCULATION PER 220.31, INCLUDE ADDED
 LOADS. THE ONE ON THE PLAN IS INCOMPLETE.
  
 7} BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP
 RECEPTACLE PER 210.11(C) (3), THE SCHEDULE ALSO
 MENTIONS GENERAL LIGHTING ON THE CIRCUIT IN VIOLATION.
  
 NOTE: IT IS PROHIBITED TO HAVE TWO COOKING FACILITIES
 IN A SINGLE FAMILY RESIDENCE. IT THE KITCHEN ON THE
 PLANS IS THE SECOND ONE IT MUST BE REMOVED. CALL ZONING
 @ 805-6720.
  
 TWO SETS OF ALL CONSTRUCTION DOCUMENTS ARE REQUIRED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]