| 2007-02-14 13:21:07 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ENGINEER OF RECORD SHALL INDICATE THE |
| | CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER |
| | INFORMATION REQUIRED BY 61G15-23.002FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH |
| | A SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND |
| | ILLUSTRATED IN SAME. |
| | |
| | 3} IF THE SERVICE IS TO BE MOVED OR UPGRADED, TH |
| | FOLLOWING IS APPLICABLE. |
| | A) SHOW THE PHYSICAL LOCATION OF ALL SERVICE |
| | EQUIPMENT ON THE PLAN. 215.5. |
| | B) PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 4} ALL RECEPTS SERVING KITCHEN COUNTERSPACE MUST BE |
| | GFI/GFIPROTECTEDAS REQUIRED PER 210.8(A)(6). INDICATE |
| | SAME ON PLAN. |
| | |
| | 5} LIST THE REQ'D ARCFAULT PROTECTED CURCUIT(S) ON |
| | PANELSCHEDULE. PLEASE SEE THAT ALL "OUTLETS"IN BEDROOMS |
| | ARE TO BE PROTECTED ,INCLUDING, LTS, RECEPTS, SD'S |
| | ETC. |
| | |
| | 6} PROVIDE A LOAD CALCULATION PER 220.31, INCLUDE ADDED |
| | LOADS. THE ONE ON THE PLAN IS INCOMPLETE. |
| | |
| | 7} BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP |
| | RECEPTACLE PER 210.11(C) (3), THE SCHEDULE ALSO |
| | MENTIONS GENERAL LIGHTING ON THE CIRCUIT IN VIOLATION. |
| | |
| | NOTE: IT IS PROHIBITED TO HAVE TWO COOKING FACILITIES |
| | IN A SINGLE FAMILY RESIDENCE. IT THE KITCHEN ON THE |
| | PLANS IS THE SECOND ONE IT MUST BE REMOVED. CALL ZONING |
| | @ 805-6720. |
| | |
| | TWO SETS OF ALL CONSTRUCTION DOCUMENTS ARE REQUIRED FOR |
| | REVIEW PER 106.1 FBC AS AMENDED. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |