| Plan Review Notes For Permit 07011242 |
| Permit Number |
07011242 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-20 16:09:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.) SHUTTER MOUNTING TYPE STATES TAPCON, BUT IT SHOULD | | | SPECIFY WHICH CONNECTION TYPE YOU ARE USING (NOT WHICH | | | ANCHOR).SOME OF THE SPANS ARE SHORTER THAN THE | | | OPENING SIZE; IS THIS AN INSIDE MOUNT?THE MOUNTING | | | TYPE ANSWERS THIS QUESTION.ANCHORING VARIES DEPENDING | | | ON WHICH MOUNTING TYPE IS USED.AS DISCUSSED, NO RESUB | | | FEE, AND HAVE THE QUALIFIER SCHEDULE AN APPOINTMENT IF | | | HE NEEDS CLARIFICATION. | | | |
|