| Date |
Text |
| 2007-02-21 18:19:54 | *****DENIED***** |
| | |
| | |
| | 1.THE COMPLETE ADDRESS OF THE JOB SITE SHALL BE IN |
| | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SEE |
| | ID1.1, LS1.1, IC1.1, ASP1.1, A1.1, A1.2, A2.1, A2.2, |
| | A2.3;E-1, E-2, E-3, E-4, M-1, M-2, M-3, M-4, M-5, AND |
| | M-6. |
| | |
| | 2.ON SHEET ID1.1, THE TYPE OF OCCUPANCY IS LISTED AS |
| | INSTITUTIONAL.CHAPTER 19 OF NFPA 101 2003 EDITION |
| | REFERENCES THIS TYPE OF OCCUPANCY AS EXISTING HEALTH |
| | CARE. |
| | |
| | 3.ON SHEET ID1.1, UNDER APPLICABLE CODES, FLORIDA |
| | FIRE PREVENTION CODE 2004 SHALL BE REFERENCED. |
| | |
| | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 6.THE BUILDING OR PORTIONS OF THE BUILDING MAYBE |
| | OCCUPIED DURING CONSTRUCTION, ALTERATIONS, OR |
| | DEMOLITION ONLY WHERE REQUIRED MEANS OF EGRESS AND |
| | REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND |
| | MAINTAINED FOR THE PORTION OCCUPIED. |
| | |
| | 7.THE INTERIOR FINISH MATERIAL FOR WALLS AND CEILINGS |
| | SHALL BE CLASS A OR CLASS B. |
| | |
| | 8.ON SHEET E-2, IT IS NOTED THAT THE SMOKE DETECTORS |
| | (SD'S) ARE TO BE REMOVED TO ALLOW THE REMOVAL OF THE |
| | CEILING AND THAT THEY ARE TO BE RE-INSTALLED AT THE |
| | SAME LOCATION ONCE THE NEW CEILING IS PLACE.WHAT IS |
| | THE ANTICIPATED TIME FRAME FOR THIS ASPECT OF THE JOB |
| | TO BE COMPLETED AS TO MINIMIZE DOWNTIME FOR THE FIRE |
| | ALARM SYSTEM? |
| | |
| | 09.UPON COMPLETION OF THE RE-INSTALLING OF THE SMOKE |
| | DETECTORS, VERIFY THEIR OPERABILITY AS PER NFPA 72. |
| | |
| | 10.AS PER WEST PALM BEACH FIRE PREVENTION,THE NEWLY |
| | INSTALLED DUCT SMOKE DETECTOR SHALL INITIATE A GENERAL |
| | FIRE ALARM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE ON THE PLANS EACH OF THE |
| | ABOVE COMMENTS WERE ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |