| 2007-04-12 16:47:53 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS |
| | ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED |
| | PER 13-103.1.1.1 |
| | PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025 |
| | |
| | 2) NOTE: PLEASE SEE THE NUMBER OF*B* FIXTURES ON |
| | PLANS DO NOT CORRELATE WITH THE NUMBER OFFIXTURES ON |
| | ENERGY CALCULATIONS.PLEASE SEE THE NUMBER OF *A* |
| | FIXTURES ALSO DO NOT CORRELATE. THESE SEEM TO BE |
| | REVERSED. PLEASE SEE THE WATTAGE ON *C* ARE 25 ON |
| | ENERGY CALCULATIONS AND AS 26 ON PLANS. |
| | PLEASE ADJUST PLANS, OR ENERGY CALCULATIONS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |