| Plan Review Notes For Permit 07011233 |
| Permit Number |
07011233 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-03 11:32:38 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEW NOTES #1 AND #2. | | | 2. SPACE ABOVE THE DROPPED CEILING IS A PLENUM PER | | | MECHANICAL PAGE M2.1, REVISE PLUMBING NOTE#11 ON PAGE | | | P0.1. PVC CANNOT BE USED. EXCEPTABLE MATERIAL WOULD BE | | | CAST IRON OR COPPER. | | | 3. WATER HAMMER ARRESTORS ARE REQUIRED ON THE HOT AND | | | COLD WATER PER SECTION 604.9, AND PER MANUFACTURE'S | | | INSTALLATION INSTRUCTIONS, AS CLOSE TO THE FIXTURE AS | | | POSSIBLE. (ONE RISER DIAGRAM MARKED IN RED) | | | 4.SHOW CLEAR FLOOR SPACE, FRONTAL APPROACH, ON FLOOR | | | PLAN AT BREAK SINK. | | | 5.PAGE A-08(2)DOES NOT CLEARLY SHOW THE FRONTAL | | | APPROACH OR MEASUREMENTS ,WIDTH/ AND HIGHT ON TOP OF | | | SINK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|