| Plan Review Notes For Permit 07011232 |
| Permit Number |
07011232 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-01 10:14:26 | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE | | | CORRECT. | | | | | | 2) RETURN AIR TRANSFER DUCTS TO CONFERENCE ROOM, OFFICE | | | #2 AND #4 ARE UNDER SIZED. BALANCED RETURN AIR MAY BE | | | ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | PER 2004 FBC/M 601.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|