| Plan Review Notes For Permit 07011226 |
| Permit Number |
07011226 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-19 14:59:40 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 2-2-07 #3, SHOW DETAIL HOW | | | 3/8" ROD IS TO BE SECURED TO "HOOD", SEE YELLOW HIGH | | | LIGHTS ON PLANS PAGE 2 OF 5. | | | | | | 2) WILL PERPENDICULAR BLOCKING NEED TO BE INSTALLED | | | BETWEEN THE TRUSSES AT ROOF PENETRATIONS? SEE YELLOW | | | HIGH LIGHTS ON PLANS PAGE 2 OF 5, IF SO PLEASE | | | CORRECT. | | | | | | 3) SEE PLANS PAGE 4 OF 5 DETAIL D-7 STATES WIND LOADS | | | OF 120 MPH, WIND LOADS FOR THIS AREA ARE 140, SEE 2004 | | | FBC 1609, PLEASE CORRECT. | | | | | | 4) SEE YELLOW HIGH LIGHTS ON PLANS PAGE 3 OF 5, PLEASE | | | SHOW MINIMUM DISTANCE FROM EF-2 TO THE ROOF PEAK AND | | | THE WALL TO COMPLY WITH 2004 FBC/M 506.3.12.3, OR IF | | | FAN IS HIGHER PLEASE STATE SO ON PLANS. | | | | | | 5) SEE YELLOW HIGH LIGHTS ON PLANS PAGE 3 OF 5, PLEASE | | | SHOW THE MINIMUM HEIGHT FOR EF-2 TO THE GABLE ROOF TO | | | COMPLY WITH 2004 FBC/M 506.3.12.1. | | | | | | 6) THE PLANS SUBMITED ARE SEALED ENGINEERED PLANS AND | | | CHANGES MAY NOT BE DONE BY HAND, PLEASE SUBMITT | | | CORRECTED PLANS WITH NO HAND MADE CHANGES TO THEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|