Plan Review Notes
Plan Review Notes For Permit 07011226
Permit Number 07011226
Review Stop M
Sequence Number 2
Notes
Date Text
2007-04-19 14:59:40*** DENIED ***
 1) AS NOTED IN LAST REVIEW 2-2-07 #3, SHOW DETAIL HOW
 3/8" ROD IS TO BE SECURED TO "HOOD", SEE YELLOW HIGH
 LIGHTS ON PLANS PAGE 2 OF 5.
  
 2) WILL PERPENDICULAR BLOCKING NEED TO BE INSTALLED
 BETWEEN THE TRUSSES AT ROOF PENETRATIONS? SEE YELLOW
 HIGH LIGHTS ON PLANS PAGE 2 OF 5, IF SO PLEASE
 CORRECT.
  
 3) SEE PLANS PAGE 4 OF 5 DETAIL D-7 STATES WIND LOADS
 OF 120 MPH, WIND LOADS FOR THIS AREA ARE 140, SEE 2004
 FBC 1609, PLEASE CORRECT.
  
 4) SEE YELLOW HIGH LIGHTS ON PLANS PAGE 3 OF 5, PLEASE
 SHOW MINIMUM DISTANCE FROM EF-2 TO THE ROOF PEAK AND
 THE WALL TO COMPLY WITH 2004 FBC/M 506.3.12.3, OR IF
 FAN IS HIGHER PLEASE STATE SO ON PLANS.
  
 5) SEE YELLOW HIGH LIGHTS ON PLANS PAGE 3 OF 5, PLEASE
 SHOW THE MINIMUM HEIGHT FOR EF-2 TO THE GABLE ROOF TO
 COMPLY WITH 2004 FBC/M 506.3.12.1.
  
 6) THE PLANS SUBMITED ARE SEALED ENGINEERED PLANS AND
 CHANGES MAY NOT BE DONE BY HAND, PLEASE SUBMITT
 CORRECTED PLANS WITH NO HAND MADE CHANGES TO THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.