2007-05-09 12:58:41** UNSAT 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW, ALONG
 WITH NEW COMMENTS NEED TO BE ADDRESSED. SOME NEW
 COMMENTS ARE BASED ON REVISED ITEMS ON RISER WHICH WERE
 NOT PART OF PREVIOUS PLANS.
 PLEASE SEE NEW COMMENTS ALSO.
  
 1) NOTE: PLEASE COORDINATE THE RISER WITH THAT OF THE
 GENERATOR EQUIPMENT, SPECS/CUT SHEETS SUBMITTED.
 PLEASE SEE THE SPECS INDICATE AN ATS AND PANEL
 COMBINATION WHICH WAS SUBMITTED ALONG WITH SPECS FOR A
 STRAIGHT ATS ONLY. PLEASE CORRELATE WHICH ONE WILL BE
 USED, HIGH-LIGHT AND ADJUST PLANS AS NEEDED.
 PLEASE SEE MISSING DISCONNECTING MEANS AS THE SPECS ARE
 UNCLEAR WHICH IS BEING USED.
 PLEASE SEE THE LOAD ON THE GENERATOR EXCEEDS THAT OF
 THE SIZE OF THE GENERATOR UNDER NATURAL AND PROPANE
 GAS.
 PLEASE SEE THE RISER HAS NOW BEEN REVISED TO SHOW 3/0
 CONDUCTOR SIZES FOR FEEDERS FROM 100AMP DISCONNECT TO
 THE ATS, ATS TO SUB PANEL AND THE FROM THE GENERATOR TO
 THE ATS. PLEASE KNOW THAT BASED ON THE BREAKER ON THE
 GENERATOR BEING AT 65AMPS, AND THE REST OF THE
 EQUIPMENT BEING SIZED AT 100AMPS, THE 3/0 CONDUCTORS
 WILL NOT FIT UNDER LUGS ETC.
 PLEASE SEE PIPE FILL OF 3/0'S IF INSTALLED AND ALSO
 TYPE OF ADAPTERS FROM 3/0'S DOWN TO LUGS UNDER THE
 BREAKERS FOR SMALLER EQUIPMENT.
 PLEASE SEE THE SPECS UNDER ONE OF THE ATS PANELS AS
 STATED WHICH REQUIRES BREAKERS FOR BEDROOM BRANCH
 CIRCUITS TO BE CHANGED OUT. (210.12)(DEPENDS ON
 EQUIPMENT USED.)
 PLEASE SEE PLUMBING REVIEW NOTES AS NO GAS RISERWAS
 SHOWN. (NOT AN ELECTRICAL COMMENT)
 PLEASE SEE SPEC SHEETS FOR GENERATOR REQUIRES SLAB TO
 BE 6 INCHES LARGER THAN THE GENERATOR IN EACH
 DIRECTION, THIS WILL AFFECT THE 24X48 SLAB AS SHOWN.
 ** PLEASE COORDINATE ALL OF THE ABOVE.
 90.7, 110.3, 310.16, 240.4, TABLES CHAPTER 9, 702.5,
 225.31-225.39. ETC
  
 2) NOTE: PLEASE INDICATE THE AIC RATINGS FOR THE NEW
 MAINS AT THE NEW SERVICE.
 110.9
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM THE MAIN DISCONNECT AT MAIN HOUSE TO THE
 CABANA DISCONNECT. 250.32, 250.110, 250.122
  
 4) NOTE: PLEASE SEE THE NEW GROUNDING ELECTRODE AT THE
 DETACHED BUILDING NOW STATES THE SLAB STEEL, PLEASE
 INDICATE THE *FOOTER* STEEL AS THE CONNECTION IS
 REQUIRED FOR THE STEEL WHICH WOULD LOCATED WITHIN THE
 2INCHES OF THE BOTTOM OF THE FOOTER. 250.50, 250.32.
 (ONLY NEED TO CHANGE THE WORDING OF SLAB TO FOOTER.)
  
 5) NOTE: PLEASE SEE THE FIRST REVIEW WHICH SPOKE OF THE
 REQUIREMENT TO SHOW THE SMOKE DEVICE AS SMOKE ALARM IF
 120V WHICH DETECTS AND SOUNDS AN ALARM. THIS WAS
 REDLINED ON THE SECOND REVIEW AND NOTED ON REVIEW ABOUT
 THE AFCI REQUIREMENT BUT NO CHANGES WERE MADE TO THE
 SYMBOL FOR THE SMOKE DEVICE. THIS COULD BE REDLINED,
 HOWEVER AS PLANS ARE COMING BACK FOR OTHER COMMENTS,
 PLEASE MAKE THE ADJUSTMENT AT THIS TIME. PLEASE SEE
 SYMBOL LEGEND, PLANS, AND PANEL SCHEDULE WHICH ALL CALL
 FOR *SMOKE DETECTOR*.
 PLEASE SEE NFPA-72 DEFINITIONS, THE FBC.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WHICH REQUESTED THE
 CODES TO BE ADDED TO THE ELECTRICAL SHEETS FOR 2005
 NFPA-70 (NEC) AND 2002 NFPA-72. ONLY THE 2002 NFPA-72
 WAS ADDED TO PLANS.
 PLEASE SEE OTHER SECTIONS OF CODES BEING QUOTED ON
 PLANS ON LIEU OF SHOWING CODE COMPLIANT DETAIL MAY NOT
 BE USED.
  
 7) NOTE: PLEASE SEE THE PANEL ON RISER MENTIONS
 32CIRCUIT PANEL, PANEL SCHEDULE SHOWS 30 CIRUCITS?
 408.4,
 FBC 106.1.2
  
 8) NOTE: PLEASE CLARIFY THE STACK WASHER AND DRYER. THE
 PLANS SHOW ONE RECEPTACLE OUTLET, YET THE PANEL
 SCHEDULE SHOWS WHAT APPEARS AS TWO SEPARATE SINGLE POLE
 CIRCUITS?
 IF THIS IS INDEED A SINGLE RECEPTACLE, WOULD THIS NOT
 BE A 2-POLE BREAKER?
 PLEASE SEE 210.4 AND THE NEXT COMMENT FOR SINGLE YOKES
 BEING FED FROM MORE THAN ONE CIRCUIT.
  
 9) NOTE: PLEASE SEE 210.4 AS THE DISHWASHER AND
 DISPOSAL IF BEING FED FROM THE SAME RECEPTACLE/YOKE
 MUST BE ON A 2-POL BREAKER. PLEASE REVISE PLANS TO SHOW
 TWO DEDICATE RECEPTACLES OR SHOW A 2-POLE BREAKER WHICH
 FEEDS THIS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  