| 2007-05-09 12:58:41 | ** UNSAT 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW, ALONG |
| | WITH NEW COMMENTS NEED TO BE ADDRESSED. SOME NEW |
| | COMMENTS ARE BASED ON REVISED ITEMS ON RISER WHICH WERE |
| | NOT PART OF PREVIOUS PLANS. |
| | PLEASE SEE NEW COMMENTS ALSO. |
| | |
| | 1) NOTE: PLEASE COORDINATE THE RISER WITH THAT OF THE |
| | GENERATOR EQUIPMENT, SPECS/CUT SHEETS SUBMITTED. |
| | PLEASE SEE THE SPECS INDICATE AN ATS AND PANEL |
| | COMBINATION WHICH WAS SUBMITTED ALONG WITH SPECS FOR A |
| | STRAIGHT ATS ONLY. PLEASE CORRELATE WHICH ONE WILL BE |
| | USED, HIGH-LIGHT AND ADJUST PLANS AS NEEDED. |
| | PLEASE SEE MISSING DISCONNECTING MEANS AS THE SPECS ARE |
| | UNCLEAR WHICH IS BEING USED. |
| | PLEASE SEE THE LOAD ON THE GENERATOR EXCEEDS THAT OF |
| | THE SIZE OF THE GENERATOR UNDER NATURAL AND PROPANE |
| | GAS. |
| | PLEASE SEE THE RISER HAS NOW BEEN REVISED TO SHOW 3/0 |
| | CONDUCTOR SIZES FOR FEEDERS FROM 100AMP DISCONNECT TO |
| | THE ATS, ATS TO SUB PANEL AND THE FROM THE GENERATOR TO |
| | THE ATS. PLEASE KNOW THAT BASED ON THE BREAKER ON THE |
| | GENERATOR BEING AT 65AMPS, AND THE REST OF THE |
| | EQUIPMENT BEING SIZED AT 100AMPS, THE 3/0 CONDUCTORS |
| | WILL NOT FIT UNDER LUGS ETC. |
| | PLEASE SEE PIPE FILL OF 3/0'S IF INSTALLED AND ALSO |
| | TYPE OF ADAPTERS FROM 3/0'S DOWN TO LUGS UNDER THE |
| | BREAKERS FOR SMALLER EQUIPMENT. |
| | PLEASE SEE THE SPECS UNDER ONE OF THE ATS PANELS AS |
| | STATED WHICH REQUIRES BREAKERS FOR BEDROOM BRANCH |
| | CIRCUITS TO BE CHANGED OUT. (210.12)(DEPENDS ON |
| | EQUIPMENT USED.) |
| | PLEASE SEE PLUMBING REVIEW NOTES AS NO GAS RISERWAS |
| | SHOWN. (NOT AN ELECTRICAL COMMENT) |
| | PLEASE SEE SPEC SHEETS FOR GENERATOR REQUIRES SLAB TO |
| | BE 6 INCHES LARGER THAN THE GENERATOR IN EACH |
| | DIRECTION, THIS WILL AFFECT THE 24X48 SLAB AS SHOWN. |
| | ** PLEASE COORDINATE ALL OF THE ABOVE. |
| | 90.7, 110.3, 310.16, 240.4, TABLES CHAPTER 9, 702.5, |
| | 225.31-225.39. ETC |
| | |
| | 2) NOTE: PLEASE INDICATE THE AIC RATINGS FOR THE NEW |
| | MAINS AT THE NEW SERVICE. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE MAIN DISCONNECT AT MAIN HOUSE TO THE |
| | CABANA DISCONNECT. 250.32, 250.110, 250.122 |
| | |
| | 4) NOTE: PLEASE SEE THE NEW GROUNDING ELECTRODE AT THE |
| | DETACHED BUILDING NOW STATES THE SLAB STEEL, PLEASE |
| | INDICATE THE *FOOTER* STEEL AS THE CONNECTION IS |
| | REQUIRED FOR THE STEEL WHICH WOULD LOCATED WITHIN THE |
| | 2INCHES OF THE BOTTOM OF THE FOOTER. 250.50, 250.32. |
| | (ONLY NEED TO CHANGE THE WORDING OF SLAB TO FOOTER.) |
| | |
| | 5) NOTE: PLEASE SEE THE FIRST REVIEW WHICH SPOKE OF THE |
| | REQUIREMENT TO SHOW THE SMOKE DEVICE AS SMOKE ALARM IF |
| | 120V WHICH DETECTS AND SOUNDS AN ALARM. THIS WAS |
| | REDLINED ON THE SECOND REVIEW AND NOTED ON REVIEW ABOUT |
| | THE AFCI REQUIREMENT BUT NO CHANGES WERE MADE TO THE |
| | SYMBOL FOR THE SMOKE DEVICE. THIS COULD BE REDLINED, |
| | HOWEVER AS PLANS ARE COMING BACK FOR OTHER COMMENTS, |
| | PLEASE MAKE THE ADJUSTMENT AT THIS TIME. PLEASE SEE |
| | SYMBOL LEGEND, PLANS, AND PANEL SCHEDULE WHICH ALL CALL |
| | FOR *SMOKE DETECTOR*. |
| | PLEASE SEE NFPA-72 DEFINITIONS, THE FBC. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTES WHICH REQUESTED THE |
| | CODES TO BE ADDED TO THE ELECTRICAL SHEETS FOR 2005 |
| | NFPA-70 (NEC) AND 2002 NFPA-72. ONLY THE 2002 NFPA-72 |
| | WAS ADDED TO PLANS. |
| | PLEASE SEE OTHER SECTIONS OF CODES BEING QUOTED ON |
| | PLANS ON LIEU OF SHOWING CODE COMPLIANT DETAIL MAY NOT |
| | BE USED. |
| | |
| | 7) NOTE: PLEASE SEE THE PANEL ON RISER MENTIONS |
| | 32CIRCUIT PANEL, PANEL SCHEDULE SHOWS 30 CIRUCITS? |
| | 408.4, |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE CLARIFY THE STACK WASHER AND DRYER. THE |
| | PLANS SHOW ONE RECEPTACLE OUTLET, YET THE PANEL |
| | SCHEDULE SHOWS WHAT APPEARS AS TWO SEPARATE SINGLE POLE |
| | CIRCUITS? |
| | IF THIS IS INDEED A SINGLE RECEPTACLE, WOULD THIS NOT |
| | BE A 2-POLE BREAKER? |
| | PLEASE SEE 210.4 AND THE NEXT COMMENT FOR SINGLE YOKES |
| | BEING FED FROM MORE THAN ONE CIRCUIT. |
| | |
| | 9) NOTE: PLEASE SEE 210.4 AS THE DISHWASHER AND |
| | DISPOSAL IF BEING FED FROM THE SAME RECEPTACLE/YOKE |
| | MUST BE ON A 2-POL BREAKER. PLEASE REVISE PLANS TO SHOW |
| | TWO DEDICATE RECEPTACLES OR SHOW A 2-POLE BREAKER WHICH |
| | FEEDS THIS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |