| 2007-04-16 09:43:49 | *** DENIED *** | | | 1) AS REQUESTED IN LAST REVIEW 2-12-07 NOTE #3,PLEASE | | | SUBMIT COMBUSTION AIR CALCULATIONS OR PROVIDE | | | COMBUSTION AIR FOR ALL NEW GAS APPLIANCES (GAS CLOTHES | | | DRYER AND GAS WATER HEATER), PER 2004 FBC/R M1701.1. | | | | | | 2) SEE GAS CLOTHES DRYER LOCATION ON PLANS, REFER TO | | | 2004 FBC/R M1701.4 PROHIBITED SOURCES. | | | COMBUSTION AIR DUCTS AND OPENINGS SHALL NOT CONNECT | | | APPLIANCE ENCLOSURES WITH SPACE IN WHICH THE OPERATION | | | OF A FAN MAY ADVERSELY AFFECT THE FLOW OF COMBUSTION | | | AIR. COMBUSTION AIR SHALL NOT BE OBTAINED FROM AN AREA | | | IN WHICH FLAMMABLE VAPORS PRESENT A HAZARD. FUEL-FIRED | | | APPLIANCES SHALL NOT OBTAIN COMBUSTION AIR FROM ANY OF | | | THE FOLLOWING ROOMS OR SPACES: | | | 1.SLEEPING ROOMS. | | | 2.BATHROOMS. | | | 3.TOILET ROOMS. | | | | | | 3) PLEASE SHOW THE LOCATION OF THE CLOTHES DRYER VENT | | | ON MECHANICAL PLANS. CLOTHES DRYER VENT TERMINATION MAY | | | NOT DISCHARGE NEAR THE A/C CONDENSER UNIT OR POOL | | | HEATER, PER 2004 FBC/M 501.2 . | | | | | | 4) PLEASE SHOW LOCATION OF A/C CONDENSER UNIT ON | | | MECHANICAL PLANS. | | | | | | 5) PLEASE BE AWARE THE GENERATOR MAY NOT BE WITHIN 5 | | | FEET OF THE DOOR TO THE STORAGE ROOM, SEE NFPA 37. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|