Plan Review Notes
Plan Review Notes For Permit 07011206
Permit Number 07011206
Review Stop M
Sequence Number 2
Notes
Date Text
2007-04-16 09:43:49*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 2-12-07 NOTE #3,PLEASE
 SUBMIT COMBUSTION AIR CALCULATIONS OR PROVIDE
 COMBUSTION AIR FOR ALL NEW GAS APPLIANCES (GAS CLOTHES
 DRYER AND GAS WATER HEATER), PER 2004 FBC/R M1701.1.
  
 2) SEE GAS CLOTHES DRYER LOCATION ON PLANS, REFER TO
 2004 FBC/R M1701.4 PROHIBITED SOURCES.
 COMBUSTION AIR DUCTS AND OPENINGS SHALL NOT CONNECT
 APPLIANCE ENCLOSURES WITH SPACE IN WHICH THE OPERATION
 OF A FAN MAY ADVERSELY AFFECT THE FLOW OF COMBUSTION
 AIR. COMBUSTION AIR SHALL NOT BE OBTAINED FROM AN AREA
 IN WHICH FLAMMABLE VAPORS PRESENT A HAZARD. FUEL-FIRED
 APPLIANCES SHALL NOT OBTAIN COMBUSTION AIR FROM ANY OF
 THE FOLLOWING ROOMS OR SPACES:
 1.SLEEPING ROOMS.
 2.BATHROOMS.
 3.TOILET ROOMS.
  
 3) PLEASE SHOW THE LOCATION OF THE CLOTHES DRYER VENT
 ON MECHANICAL PLANS. CLOTHES DRYER VENT TERMINATION MAY
 NOT DISCHARGE NEAR THE A/C CONDENSER UNIT OR POOL
 HEATER, PER 2004 FBC/M 501.2 .
  
 4) PLEASE SHOW LOCATION OF A/C CONDENSER UNIT ON
 MECHANICAL PLANS.
  
 5) PLEASE BE AWARE THE GENERATOR MAY NOT BE WITHIN 5
 FEET OF THE DOOR TO THE STORAGE ROOM, SEE NFPA 37.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.