Plan Review Notes
Plan Review Notes For Permit 07011206
Permit Number 07011206
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-13 14:43:42** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE THAT AS THE PLANS HAVE SUBSTANTIALLY
 CHANGED FROM PREVIOUSLY SUBMITTED PLANS, THERE ARE NEW
 COMMENTS.
 NOTES ON PREVIOUS REVIEW MENTION AS THERE WERE SEVERAL
 ITEMS NOT SUBMITTED FOR REVIEW THERE MAY BE NEW
 COMMENTS ON THIS REVIEW.
  
 1) NOTE:PLEASE SUBMIT ONLY THE MANUFACTURES SPECS/CUT
 SHEETS WHICH INDICATE THE MAIN EQUIPMENT FOR THE
 GENERATOR AND ATS. PLEASE SEE THE DOCUMENTS WHICH ARE
 THE MAINTENANCE AND PARTS LIST SHEETS ARE NOT NEEDED.
 PLEASE BE SURE THE SPECS INDICATE THE MINIMUM
 CLEARANCES FOR THE EQUIPMENT AND SURROUNDING
 CLEARANCE.
 PLEASE KNOW THAT THE LATEST INFORMATION FROM GENERAC IS
 THAT THIS PARTICULAR EQUIPMENT REQUIRES A MINIMUM OF
 3FT AROUND EQUIPMENT FOR PROPER VENTILATION. PLEASE SEE
 THE GENERATOR AT THIS TIME IS SHOWN TOO CLOSE TO
 DWELLING. PLEASE ALSO SEE MECHANICAL COMMENTS FOR
 MINIMUM CLEARANCES FOR EXHAUST WHICH MAY BE REQUIRED TO
 BE 5FT FROM OPENING INTO BUILDING.
 ** PLEASE BE SURE TO REVISE ALL SHEETS WHICH INDICATE
 THIS LOCATION OF THE GENERATOR ETC.
 110.3, 90.7.
 FBC 106.1.2
  
 2) NOTE: PLEASE INDICATE THE MINIMUM LEVEL FOR THE
 GENERATOR WHICH IS REQUIRED TO BE A MINIMUM OF 6INCHES
 ABOVE THE BFE.
 PLEASE SEE THE PLANS INDICATE THIS IN A FLOOD ZONE A5,
 AND BEFORE FINAL AN ELEVATION CERTIFICATE WILL BE
 REQUIRED FOR EQUIPMENT AND GENERATOR.
  
 3) NOTE: PLEASE SEE NEW RISER DIAGRAM WHICH IS NOW
 SUBMITTED FOR REVIEW FOR THE FIRST TIME.
 PLEASE SEE 250.6 AND 250.24B AS *EQUIPMENT GROUNDING
 CONDUCTORS* ARE NOT TO BE INSTALLED BEFORE THE FIRST
 MEANS OF DISCONNECT. THIS CREATES OBJECTIONABLE
 CURRENT.
 PLEASE SEE RISER AND ADJUST.
  
 4) NOTE: PLEASE SEE THE RISER DOES NOT INCLUDE THE
 GROUNDING ELECTRODE SYSTEM AT THE DETACHED BUILDING AS
 REQUIRED PER 250.32.
 PLEASE SEE 250.50 AND 250.66. *QUOTING THE CODE IN LIEU
 OF SHOWING SPECIFIC DETAIL IS NOT PERMITTED. PLEASE
 SHOW DETAIL OF THIS.
  
 5) NOTE: PLEASE SEE RISER AND NEW PANEL. PLEASE
 INDICATE HOW THE NEW ATS IS BEING FED. PLEASE SEE THE
 PANEL SCHEDULE FOR THE CABANA SHOWS ALL OF THE CIRCUITS
 BEING FED FROM THIS PANEL AND NOT CIRCUITS FROM THE NEW
 ATS PANEL????
 PLEASE INDICATE THE OCP TO NEW ATS PANEL. PLEASE
 INDICATE THE CIRCUITS AND LOADS WHICH ARE BEING
 PROPOSED ON THIS NEW ATS PANEL.
 PLEASE SEE NO CONDUCTORS, OCP ETC ARE BEING SHOWN ON
 PANEL?
 PLEASE COMPLETE.
 408.4, 240.4, 310.16 ETC.
 FBC 106.3.5.4
  
 6) NOTE: PLEASE CORRELATE PLANS FOR NEW ATS PANEL
 LOCATION. PLEASE SEE SHEET A-2 WHICH INDICATES THE
 ATS/PANEL OUTSIDE, YET THIS PANEL IS AN INDOOR PANEL
 WHICH IS LISTED AND RATED AS A NEMA 1 PANEL. PLEASE
 KNOW, IF LOCATING THE ATS PANEL OUTSIDE, PLEASE INCLUDE
 SPECS FOR THE ATS WHICH IS RATED FOR NEMA 3 LOCATIONS.
 PLEASE SEE ELECTRICAL PLANS INDICATE THIS SAME
 EQUIPMENT INSIDE??
 PLEASE CORRELATE.
 110.3, 90.7
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 422.13 WHICH REQUIRES ALL ELECTRIC
 TYPE WATER HEATERS LOADS TO BE SHOWN AT 125%. PLEASE
 SEE THE 2005 NEC.
  
 8) NOTE: PLEASE INDICATE THE FOLLOWING APPROPRIATE
 CODES ON THE ELECTRICAL SHEETS.
 2005 NFPA-70 (NEC) AND 2002 NFPA-72.
  
 9) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED BATH
 CIRCUITS PER 210.52D, 210.11C3.
 PLEASE SEE THAT THE SIZE OF THE BRANCH CIRCUIT AS SHOWN
 ON PLANS IS NOT CORRECT.
  
 10) NOTE: PLEASE CLARIFY THE STACK WASHER DRYER ON LOAD
 CALCULATIONS, AS THIS IS SHOWN AS 2-POLE 30AMP ON PANEL
 SCHEDULE? PLEASE CLARIFY.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE 210.12 AS AFCI PROTECTION IS
 REQUIRED ON THE SMOKE ALARM DEVICE(S). THIS SHOULD BE
 ON ONE OF THE OTHER CIRCUITS AS SHOWN ON PLANS. PLEASE
 ALSO SEE THAT THE PLANS INDICATE THE DEVICE AS A SMOKE
 DETECTOR AND THE PANEL SCHEDULE INDICATES SMOKE ALARMS.
 PLEASE COORDINATE.
  
 12) NOTE: PLEASE BE SURE THE SEAL FROM DESIGNER OF
 RECORD IS CLEAR AND VISIBLE WITH ALL INFORMATION ON
 SAID SEAL.
 FS481.221
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved