| Date |
Text |
| 2007-04-13 14:43:42 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THAT AS THE PLANS HAVE SUBSTANTIALLY |
| | CHANGED FROM PREVIOUSLY SUBMITTED PLANS, THERE ARE NEW |
| | COMMENTS. |
| | NOTES ON PREVIOUS REVIEW MENTION AS THERE WERE SEVERAL |
| | ITEMS NOT SUBMITTED FOR REVIEW THERE MAY BE NEW |
| | COMMENTS ON THIS REVIEW. |
| | |
| | 1) NOTE:PLEASE SUBMIT ONLY THE MANUFACTURES SPECS/CUT |
| | SHEETS WHICH INDICATE THE MAIN EQUIPMENT FOR THE |
| | GENERATOR AND ATS. PLEASE SEE THE DOCUMENTS WHICH ARE |
| | THE MAINTENANCE AND PARTS LIST SHEETS ARE NOT NEEDED. |
| | PLEASE BE SURE THE SPECS INDICATE THE MINIMUM |
| | CLEARANCES FOR THE EQUIPMENT AND SURROUNDING |
| | CLEARANCE. |
| | PLEASE KNOW THAT THE LATEST INFORMATION FROM GENERAC IS |
| | THAT THIS PARTICULAR EQUIPMENT REQUIRES A MINIMUM OF |
| | 3FT AROUND EQUIPMENT FOR PROPER VENTILATION. PLEASE SEE |
| | THE GENERATOR AT THIS TIME IS SHOWN TOO CLOSE TO |
| | DWELLING. PLEASE ALSO SEE MECHANICAL COMMENTS FOR |
| | MINIMUM CLEARANCES FOR EXHAUST WHICH MAY BE REQUIRED TO |
| | BE 5FT FROM OPENING INTO BUILDING. |
| | ** PLEASE BE SURE TO REVISE ALL SHEETS WHICH INDICATE |
| | THIS LOCATION OF THE GENERATOR ETC. |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE INDICATE THE MINIMUM LEVEL FOR THE |
| | GENERATOR WHICH IS REQUIRED TO BE A MINIMUM OF 6INCHES |
| | ABOVE THE BFE. |
| | PLEASE SEE THE PLANS INDICATE THIS IN A FLOOD ZONE A5, |
| | AND BEFORE FINAL AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED FOR EQUIPMENT AND GENERATOR. |
| | |
| | 3) NOTE: PLEASE SEE NEW RISER DIAGRAM WHICH IS NOW |
| | SUBMITTED FOR REVIEW FOR THE FIRST TIME. |
| | PLEASE SEE 250.6 AND 250.24B AS *EQUIPMENT GROUNDING |
| | CONDUCTORS* ARE NOT TO BE INSTALLED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. THIS CREATES OBJECTIONABLE |
| | CURRENT. |
| | PLEASE SEE RISER AND ADJUST. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER DOES NOT INCLUDE THE |
| | GROUNDING ELECTRODE SYSTEM AT THE DETACHED BUILDING AS |
| | REQUIRED PER 250.32. |
| | PLEASE SEE 250.50 AND 250.66. *QUOTING THE CODE IN LIEU |
| | OF SHOWING SPECIFIC DETAIL IS NOT PERMITTED. PLEASE |
| | SHOW DETAIL OF THIS. |
| | |
| | 5) NOTE: PLEASE SEE RISER AND NEW PANEL. PLEASE |
| | INDICATE HOW THE NEW ATS IS BEING FED. PLEASE SEE THE |
| | PANEL SCHEDULE FOR THE CABANA SHOWS ALL OF THE CIRCUITS |
| | BEING FED FROM THIS PANEL AND NOT CIRCUITS FROM THE NEW |
| | ATS PANEL???? |
| | PLEASE INDICATE THE OCP TO NEW ATS PANEL. PLEASE |
| | INDICATE THE CIRCUITS AND LOADS WHICH ARE BEING |
| | PROPOSED ON THIS NEW ATS PANEL. |
| | PLEASE SEE NO CONDUCTORS, OCP ETC ARE BEING SHOWN ON |
| | PANEL? |
| | PLEASE COMPLETE. |
| | 408.4, 240.4, 310.16 ETC. |
| | FBC 106.3.5.4 |
| | |
| | 6) NOTE: PLEASE CORRELATE PLANS FOR NEW ATS PANEL |
| | LOCATION. PLEASE SEE SHEET A-2 WHICH INDICATES THE |
| | ATS/PANEL OUTSIDE, YET THIS PANEL IS AN INDOOR PANEL |
| | WHICH IS LISTED AND RATED AS A NEMA 1 PANEL. PLEASE |
| | KNOW, IF LOCATING THE ATS PANEL OUTSIDE, PLEASE INCLUDE |
| | SPECS FOR THE ATS WHICH IS RATED FOR NEMA 3 LOCATIONS. |
| | PLEASE SEE ELECTRICAL PLANS INDICATE THIS SAME |
| | EQUIPMENT INSIDE?? |
| | PLEASE CORRELATE. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE 422.13 WHICH REQUIRES ALL ELECTRIC |
| | TYPE WATER HEATERS LOADS TO BE SHOWN AT 125%. PLEASE |
| | SEE THE 2005 NEC. |
| | |
| | 8) NOTE: PLEASE INDICATE THE FOLLOWING APPROPRIATE |
| | CODES ON THE ELECTRICAL SHEETS. |
| | 2005 NFPA-70 (NEC) AND 2002 NFPA-72. |
| | |
| | 9) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED BATH |
| | CIRCUITS PER 210.52D, 210.11C3. |
| | PLEASE SEE THAT THE SIZE OF THE BRANCH CIRCUIT AS SHOWN |
| | ON PLANS IS NOT CORRECT. |
| | |
| | 10) NOTE: PLEASE CLARIFY THE STACK WASHER DRYER ON LOAD |
| | CALCULATIONS, AS THIS IS SHOWN AS 2-POLE 30AMP ON PANEL |
| | SCHEDULE? PLEASE CLARIFY. |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE 210.12 AS AFCI PROTECTION IS |
| | REQUIRED ON THE SMOKE ALARM DEVICE(S). THIS SHOULD BE |
| | ON ONE OF THE OTHER CIRCUITS AS SHOWN ON PLANS. PLEASE |
| | ALSO SEE THAT THE PLANS INDICATE THE DEVICE AS A SMOKE |
| | DETECTOR AND THE PANEL SCHEDULE INDICATES SMOKE ALARMS. |
| | PLEASE COORDINATE. |
| | |
| | 12) NOTE: PLEASE BE SURE THE SEAL FROM DESIGNER OF |
| | RECORD IS CLEAR AND VISIBLE WITH ALL INFORMATION ON |
| | SAID SEAL. |
| | FS481.221 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |