Plan Review Notes
Plan Review Notes For Permit 07011206
Permit Number 07011206
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-19 16:31:43BUILDING REVIEW SECOND CHECKLIST:
 1- NEW GENERATOR: ADDRESS COMMENTS BY ELECTRICAL AND
 MECHANICAL PLAN REVIEWERS REGARDING LOCATION NEAR
 OPENINGS AND EQUIPMENT CLEARANCES.
  
 2- PROVIDE COMPLETE SPECS FROM BBQ AND HOOD
 MANUFACTURER STATING THAT LOCATION OF THIS EQUIPMENT
 NEXT TO A WINDOW IS OK. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 3- BRING DRAWINGS TO PALM BEACH COUNTY TO SEE IF IMPACT
 FEES ARE DUE OR NOT. THEY ARE THE ONES WHO DETERMINE IF
 IMPACT FEES ARE DUE OR NOT.LETTER SUBMITTED IS ONLY
 TO STATE THAT THERE WAS A BUILDING IN THIS LOCATION.
 SHOWLETTER TO PALM BEACH COUNTY TO SEE WHAT CREDIT IS
 GRANTED. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED.SEC. 713.13
 FLORIDA STATUTE. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 5- SHEET A-2:MISSING THE COVERED PORCH AREA IN THE
 TOTAL AREA CALCULATIONS.PROVIDE INFORMATION AS
 REQUIRED.
  
 6- SHEET A-6: NEED TO REVISE THE DESIGN PRESSURES. NEED
 TO USE REVISED TABLE 1609.6.2.1(2) OF FBC 2004, NOT
 TABLE 1609.6B.
  
 7- SUBMITTED DRAWINGS ARE TOO DARK AND THEY WON'T BE
 ABLE TO BE COPIED FOR CITY RETENTION FILES. PROVIDE
 CLEAR AND LEGIBLE DRAWINGS AS REQUIRED BY SEC. 106.1.3
 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712