| 2007-04-19 16:31:43 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- NEW GENERATOR: ADDRESS COMMENTS BY ELECTRICAL AND |
| | MECHANICAL PLAN REVIEWERS REGARDING LOCATION NEAR |
| | OPENINGS AND EQUIPMENT CLEARANCES. |
| | |
| | 2- PROVIDE COMPLETE SPECS FROM BBQ AND HOOD |
| | MANUFACTURER STATING THAT LOCATION OF THIS EQUIPMENT |
| | NEXT TO A WINDOW IS OK. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 3- BRING DRAWINGS TO PALM BEACH COUNTY TO SEE IF IMPACT |
| | FEES ARE DUE OR NOT. THEY ARE THE ONES WHO DETERMINE IF |
| | IMPACT FEES ARE DUE OR NOT.LETTER SUBMITTED IS ONLY |
| | TO STATE THAT THERE WAS A BUILDING IN THIS LOCATION. |
| | SHOWLETTER TO PALM BEACH COUNTY TO SEE WHAT CREDIT IS |
| | GRANTED. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. |
| | |
| | 4- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF |
| | BEING RECORDED IF WORK IS NOT STARTED.SEC. 713.13 |
| | FLORIDA STATUTE. NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 5- SHEET A-2:MISSING THE COVERED PORCH AREA IN THE |
| | TOTAL AREA CALCULATIONS.PROVIDE INFORMATION AS |
| | REQUIRED. |
| | |
| | 6- SHEET A-6: NEED TO REVISE THE DESIGN PRESSURES. NEED |
| | TO USE REVISED TABLE 1609.6.2.1(2) OF FBC 2004, NOT |
| | TABLE 1609.6B. |
| | |
| | 7- SUBMITTED DRAWINGS ARE TOO DARK AND THEY WON'T BE |
| | ABLE TO BE COPIED FOR CITY RETENTION FILES. PROVIDE |
| | CLEAR AND LEGIBLE DRAWINGS AS REQUIRED BY SEC. 106.1.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |