| Notes |
| Date |
Text |
| 2007-02-13 08:32:20 | DENIED; | | | 1. SANITARY RISER DIAGRAM; | | | A) SINKS AND W/M TO DISCHARGE DOWN STREAM OF THE | | | BATHROOM SINK. SECTION 909.1 WET VENTS. | | | B) AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE | | | 3" WITH A C.O. AT 48" AFF. VENT REQUIRED. | | | 2. SHOW ON PLANS THE TYPE OF THERMAL EXPANSION CONTROL | | | TO BE USED . SECTION 607.3. | | | 3.ADD NOTE TO PLAN, HOT WATER PIPES TO BE INSULATED, | | | PER ENERGY CODE SECTION 13-612.1. | | | 4. PLANS MUST BE APPROVED BY ZONING BEFORE PLUMBING | | | PLAN REVIEW CAN BE COMPLETE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|