| Plan Review Notes For Permit 07011206 |
| Permit Number |
07011206 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-12 14:36:25 | *** DENIED *** | | | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR | | | REVIEW. PLEASE SUBMIT MECHANICAL PLANS | | | FOR REVIEW, PER 2004 FBC WPB AMEND. 106.3.5.4. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) PLEASE SUBMIT COMBUSTION AIR CALCULATIONS OR | | | COMBUSTION AIR FOR ALL NEW GAS APPLIANCES, PER 2004 | | | FBC/R M1701.1. | | | | | | 4) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND | | | INSTALLATION INSTRUCTIONS FOR GAS BBQ GRILL AND HOOD. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|