| Date |
Text |
| 2007-02-08 09:31:03 | ***** UNSAT ***** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE FOLLOWING |
| | MINIMUM CODES FOR DESIGN. |
| | 2005 NFPA-70 AND THE 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE ZONING COMMENTS FOR THE SIZE OF THE |
| | STRUCTURE ALONG WITH THE SEPARATE METERED SERVICE WHICH |
| | IS NOT PERMITTED AS THIS IS ZONED SF-7. |
| | PLEASE SEE COMMENTS ALSO WITH RESPECT TO THE LOCATION |
| | OF THE GENERATOR. |
| | PLEASE KNOW AT THIS TIME THE RISER WILL NEED TO BE |
| | COMPLETELY REVISED TO FEED THE NEW CABANA FROM THE |
| | EXISTING HOUSE. |
| | |
| | 3) NOTE: PLEASE SEE THAT LOCATION OF THE GENERATOR IS |
| | NOT PERMITTED PER ZONING, PLEASE ALSO SHOW AND INDICATE |
| | ALL DISTANCES FROM ALL SURROUNDING WALLS, WINDOWS, |
| | SOFFIT OPENINGS ETC. |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | PROPOSED GENERATOR, ATS ETC. WHAT IS THE PRIME-MOVER? |
| | PLEASE BE SURE THE MANUFACTURES CUT SHEETS INDICATE THE |
| | MINIMUM CLEARANCES REQUIRED. |
| | PLEASE SEE THAT THE ATS SHALL BE SERVICE ENTRANCE |
| | RATED, MEANS OF DISCONNECT FOR THE GENERATOR SHALL MEET |
| | 702.6, 702.11 |
| | 90.7, 110.3, 230.70, 230.76, 230.79 ETC |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE RISER WHICH SHOWS AND EQUIPMENT |
| | GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS |
| | OF DISCONNECT. PLEASE KNOW THAT EVEN THOUGH THE METER |
| | IS COMING OUT, PLEASE KNOW THAT IN ANY CASE AN * |
| | EQUIPMENT GROUNDING CONDUCTOR* IS NOT INSTALLED UNTIL |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | 250.6, 250.24 |
| | |
| | 5) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI |
| | RECEPTACLES AS THIS IS BEING NOTED AS A KITCHEN WITH |
| | SMALL APPLIANCE CIRCUITS ETC. |
| | PLEASE SEE 210.52C1-5. MISSING COUNTER AND PENINSULAR. |
| | |
| | 6) NOTE: PLEASE SEE NFPA-72 11.8.3 AS A SMOKE DETECTOR |
| | OR SMOKE ALARM IS NOT PERMITTED WITHIN 20FT OF ANY |
| | COOKING APPLIANCES UNLESS MEETING THE EXCEPTIONS OF |
| | THIS SECTION FOR THE TYPE OF DEVICE BEING INSTALLED. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | 7) NOTE: PLEASE CLARIFY THE PLANS WHICH INDICATE A |
| | STACK WASHER /DRYER. PLEASE SEE COMMENT WITH RESPECT TO |
| | MISSING PANEL SCHEDULE BELOW. |
| | 106.1.2 |
| | |
| | 8) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR |
| | ALL CIRCUITS, OVER CURRENT PROTECTION DEVICES AND |
| | CONDUCTOR SIZES SHOWING ALL OF THE MINIMUM REQUIRED |
| | CIRCUITS. |
| | 210.52, 210.11, 220, 408.4. PLEASE SEE THE FOLLOWING |
| | TEXT FROM THE CODE COMMENTARY WHICH STATES * THE CODE |
| | TO REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION. |
| | |
| | 9) NOTE: PLEASE SUBMIT THE FOLLOWING INFORMATION WHEN |
| | RISER IS REVISED WHICH WILL BE FED FROM THE MAIN HOUSE |
| | SERVICE. PLEASE INDICATE THE OVER CURRENT PROTECTION |
| | FOR NEW FEEDERS FROM THE EXISTING SERVICE. PLEASE |
| | SUBMIT COMPLETE LOAD CALCULATIONS ON THE EXISTING |
| | SERVICE WHICH WILL INCLUDE THE LOADS FOR THE NEW. |
| | SHOW ALL FEEDERS AND GROUNDING ELECTRODE SYSTEM. ETC |
| | DISCONNECTING MEANS AT THE DETACHED BUILDING ETC. |
| | 215.5, 220, 240.4, 408.4, 310.16, 250.32, 225.31 ETC |
| | 106.1.2, 106.3.5.4 |
| | |
| | 10) NOTE: PLEASE BE SURE TO INCLUDE THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER 210.52D, 210.11C3. |
| | MUST BE 20AMP AND #12. |
| | |
| | 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION PER |
| | 210.12B. (THE AREA OUTSIDE KITCHEN IS BEING CONSIDERED |
| | ADAPTABLE SLEEPING ROOM WHICH WILL REQUIRE THIS |
| | PROTECTION FOR ALL OUTLETS). |
| | |
| | 12) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER |
| | ON THE TITLE BLOCKS FOR THE DESIGNER OF RECORD ON |
| | SHEETS. |
| | FAC 61G1-16.004 |
| | |
| | 13) NOTE: PLEASE SEE THE ADDRESS AS ASSIGNED IS 122 AS |
| | THE PREVIOUS HOUSE AT 126 IS NO LONGER PRESENT AND THIS |
| | IS NOW PART OF THE 122 LEGAL ADDRESSED PROPERTIES. |
| | PLEASE ADJUST TITLE BLOCKS. |
| | |
| | 14) NOTE: PLEASE KNOW THAT AT THIS TIME AS THERE ARE |
| | MANY ITEMS WHICH WERE NOT SUBMITTED AND THERE ARE ITEMS |
| | WHICH CAN NOT BE REVIEWED FOR CODE COMPLIANCE THERE MAY |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE NOT |
| | PRESENT ON THIS REVIEW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-07 16:55:02 | IN ELEC FOR REVIEW. |