Notes
Date Text
2007-02-08 09:31:03***** UNSAT *****
  
  
 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE FOLLOWING
 MINIMUM CODES FOR DESIGN.
 2005 NFPA-70 AND THE 2002 NFPA-72
  
 2) NOTE: PLEASE SEE ZONING COMMENTS FOR THE SIZE OF THE
 STRUCTURE ALONG WITH THE SEPARATE METERED SERVICE WHICH
 IS NOT PERMITTED AS THIS IS ZONED SF-7.
 PLEASE SEE COMMENTS ALSO WITH RESPECT TO THE LOCATION
 OF THE GENERATOR.
 PLEASE KNOW AT THIS TIME THE RISER WILL NEED TO BE
 COMPLETELY REVISED TO FEED THE NEW CABANA FROM THE
 EXISTING HOUSE.
  
 3) NOTE: PLEASE SEE THAT LOCATION OF THE GENERATOR IS
 NOT PERMITTED PER ZONING, PLEASE ALSO SHOW AND INDICATE
 ALL DISTANCES FROM ALL SURROUNDING WALLS, WINDOWS,
 SOFFIT OPENINGS ETC.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR THE
 PROPOSED GENERATOR, ATS ETC. WHAT IS THE PRIME-MOVER?
 PLEASE BE SURE THE MANUFACTURES CUT SHEETS INDICATE THE
 MINIMUM CLEARANCES REQUIRED.
 PLEASE SEE THAT THE ATS SHALL BE SERVICE ENTRANCE
 RATED, MEANS OF DISCONNECT FOR THE GENERATOR SHALL MEET
 702.6, 702.11
 90.7, 110.3, 230.70, 230.76, 230.79 ETC
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE RISER WHICH SHOWS AND EQUIPMENT
 GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT. PLEASE KNOW THAT EVEN THOUGH THE METER
 IS COMING OUT, PLEASE KNOW THAT IN ANY CASE AN *
 EQUIPMENT GROUNDING CONDUCTOR* IS NOT INSTALLED UNTIL
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.6, 250.24
  
 5) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI
 RECEPTACLES AS THIS IS BEING NOTED AS A KITCHEN WITH
 SMALL APPLIANCE CIRCUITS ETC.
 PLEASE SEE 210.52C1-5. MISSING COUNTER AND PENINSULAR.
  
 6) NOTE: PLEASE SEE NFPA-72 11.8.3 AS A SMOKE DETECTOR
 OR SMOKE ALARM IS NOT PERMITTED WITHIN 20FT OF ANY
 COOKING APPLIANCES UNLESS MEETING THE EXCEPTIONS OF
 THIS SECTION FOR THE TYPE OF DEVICE BEING INSTALLED.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 7) NOTE: PLEASE CLARIFY THE PLANS WHICH INDICATE A
 STACK WASHER /DRYER. PLEASE SEE COMMENT WITH RESPECT TO
 MISSING PANEL SCHEDULE BELOW.
 106.1.2
  
 8) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR
 ALL CIRCUITS, OVER CURRENT PROTECTION DEVICES AND
 CONDUCTOR SIZES SHOWING ALL OF THE MINIMUM REQUIRED
 CIRCUITS.
 210.52, 210.11, 220, 408.4. PLEASE SEE THE FOLLOWING
 TEXT FROM THE CODE COMMENTARY WHICH STATES * THE CODE
 TO REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.
  
 9) NOTE: PLEASE SUBMIT THE FOLLOWING INFORMATION WHEN
 RISER IS REVISED WHICH WILL BE FED FROM THE MAIN HOUSE
 SERVICE. PLEASE INDICATE THE OVER CURRENT PROTECTION
 FOR NEW FEEDERS FROM THE EXISTING SERVICE. PLEASE
 SUBMIT COMPLETE LOAD CALCULATIONS ON THE EXISTING
 SERVICE WHICH WILL INCLUDE THE LOADS FOR THE NEW.
 SHOW ALL FEEDERS AND GROUNDING ELECTRODE SYSTEM. ETC
 DISCONNECTING MEANS AT THE DETACHED BUILDING ETC.
 215.5, 220, 240.4, 408.4, 310.16, 250.32, 225.31 ETC
 106.1.2, 106.3.5.4
  
 10) NOTE: PLEASE BE SURE TO INCLUDE THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER 210.52D, 210.11C3.
 MUST BE 20AMP AND #12.
  
 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION PER
 210.12B. (THE AREA OUTSIDE KITCHEN IS BEING CONSIDERED
 ADAPTABLE SLEEPING ROOM WHICH WILL REQUIRE THIS
 PROTECTION FOR ALL OUTLETS).
  
 12) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 ON THE TITLE BLOCKS FOR THE DESIGNER OF RECORD ON
 SHEETS.
 FAC 61G1-16.004
  
 13) NOTE: PLEASE SEE THE ADDRESS AS ASSIGNED IS 122 AS
 THE PREVIOUS HOUSE AT 126 IS NO LONGER PRESENT AND THIS
 IS NOW PART OF THE 122 LEGAL ADDRESSED PROPERTIES.
 PLEASE ADJUST TITLE BLOCKS.
  
 14) NOTE: PLEASE KNOW THAT AT THIS TIME AS THERE ARE
 MANY ITEMS WHICH WERE NOT SUBMITTED AND THERE ARE ITEMS
 WHICH CAN NOT BE REVIEWED FOR CODE COMPLIANCE THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE NOT
 PRESENT ON THIS REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-07 16:55:02IN ELEC FOR REVIEW.