Plan Review Notes For Permit 07011202
Permit Number 07011202
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-03-07 17:35:38*****DENIED*****
  
  
 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.MAY
 BE ADDED TO SHEET A-5.1
  
 03.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR
 THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES).
 MAY BE ADDED TO SHEET A-5.1
  
 04.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION FRONTING OKEECHOBEE BOULEVARD.AS
 PER WEST PALM BEACH CODE, NUMERALS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH AND SHALL BE OF A
 COLOR IN DIRECT CONTRAST TO AND CLEARLY DISTINGUISHABLE
 FROM ITS BACKGROUND.ILLUSTRATE ON SHEET A-6.1,
 DIAGRAM # 03(DO NOT PLACE NUMBERS ON DOORS)
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722