| Plan Review Notes For Permit 07011175 |
| Permit Number |
07011175 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-02-11 08:57:40 | DENIED; | | | 1. PAGE P-1 BUILDING CONTRACTOR NOTE; PLUMBING CODE TO | | | BE USED IS THE FBC-PLUMBING SECTION 601, NOT THE | | | RESIDENTIAL CODE 2901 THIS IS A BUSINESS. | | | 2. WATER RISER DIAGRAM SHALL BE OF SUFFICIENT CLARITY, | | | FBC BUILDING CHAPTER 1 (ADMINISTRATION) SECTION | | | 106.1.1. DELETE SANITARY DIAGRAM ( UNDER WATER DIAGRAM) | | | , AND SHOW WATER SERVICE FROM SHUTOFF VALVE TO THE LAST | | | FIXTURE IN BUILDING. | | | 3. ADD NOTE TO WATER RISER DIAGRAM; " BACKFLOW | | | PREVENTER REQUIRED ON WATER SERVICE AT CITY WATER | | | METER". | | | 4. SANITARY RISER DIAGRAM; 3 COMPARTMENT SINK SHALL | | | DISCHARGE DOWN STREAM OF THE BATHROOM GROUP SEE FBC | | | PLUMBING SECTION 909.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|