| Plan Review Notes For Permit 07011175 |
| Permit Number |
07011175 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-11-20 09:43:22 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEWER'S COMMENT # 13. | | | 2. INFORMATION ON CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY. FBC BUILDING CHAPTER 1 | | | (ADMINISTRATION) SECTION 106.1.1. | | | A) SEPARATE WATER AND SANITARY RISER | | | DIAGRAMS. | | | 1. SANITARY RISER DIAGRAM; | | | A)CLEARLY MARK EACH FIXTURE, | | | I.E. LAV, W/C, SINK. | | | B) DRAIN SIZES ARE NOT CORRECT. | | | LAVATORY'S ARE 1 1/4 SINKS ARE 1 1/2. | | | 2. WATER RISER DIAGRAM; | | | A) SHOW CALCULATIONS FOR WATER | | | DISTRIBUTION PIPING . SEE FBC PLUMBING TABLE 603.1. | | | B) SHOW SIZE OF WATER HEATER. | | | 3. SHOW DETAIL DRAWINGS OF HANDICAP FIXTURES WITH ALL | | | REQUIRED MESUREMENTS. ( LAV., W/C, D/F ) | | | 4. SHOW DETAIL DRAWINGS FOR CHILDRENS BATHROOMS AND | | | SPECK OUT FIXTURES. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|