| 2007-11-11 12:49:33 | REVIEW #: 3 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | *NOTE* A WRITTEN RESPONSE TO REVIEW COMMENTS FROM THE |
| | DESIGN TEAM WILL AID IN THE REVIEW PROCESS. |
| | |
| | 1. ENERGY CALCULATIONS FORM 600 HAS BEEN SUBMITTED FOR |
| | THE 3RD TIME. THIS IS NOT A RESIDENTIAL OCCUPANCY, |
| | THERE IS A CHANGE OF OCCUPANCY AND SHALL THEREFORE THIS |
| | PROJECT SHALL DEMONSTRATE COMPLIANCE WITH FBC |
| | 13-101.3. |
| | |
| | 2. RETURN AIR TRANSFER DUCTS ARE STILL NOT DESIGNED TO |
| | MEET TH BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. A |
| | FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO |
| | DETERMINE IF PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS |
| | ARE AT 0.01IN. WC OR LESS IN ACCORDANCE WITH THIS |
| | SECTION. THIS STEP WILL NOT BE NECESSARY IF TRANSFERS |
| | ARE DESIGNED TO MEET THE FOLLOWING EXCEPTION: "TRANSFER |
| | DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN |
| | TRANSFER ONE AND ONE-HALF TIMES THE CROSS-SECTIONAL |
| | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE |
| | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT |
| | LEAST AN UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER |
| | RETURN AIR BALANCE." |
| | |
| | 3. NATURAL VENTILATION AS SHOWN ON PLANS IS OK. |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. OK |
| | |