| Date |
Text |
| 2007-10-22 18:33:51 | 2007-10-22 18:33:51 |
| | |
| | *** DENIED 3RD REVIEW *** |
| | |
| | 1) NOTE: ** THIS IS THE FIRST REVIEW UNDER A NEW DESIGN |
| | TEAM AND ALL NEW PLANS WERE SUBMITTED. |
| | |
| | ** PLEASE SEE HOWEVER THERE ARE SEVERAL COMMENTS FROM |
| | THE TWO PREVIOUS REVIEWS WHICH ARE THE SAME AND STILL |
| | APPLY. THERE ARE MANY OF THESE WHICH HAVE NOT BEEN |
| | ADDRESSED AND THERE ARE SOME NEW COMMENTS ONCE AGAIN |
| | DUE TO THE FACT THAT THERE ARE COMPLETELY NEW PLANS |
| | SUBMITTED. |
| | |
| | ** PLEASE KNOW AS THERE IS STILL INFORMATION NOT |
| | SUBMITTED OR DESIGNED INTO THE PLANS FOR *MINIMUM* CODE |
| | COMPLIANCE, AND A FULL AND COMPLETE REVIEW CAN NOT BE |
| | DONE. THE REVIEW COMMENTS CAN ONLY BE BASED ON PLANS |
| | AND DOCUMENTS SUBMITTED. |
| | |
| | 2) NOTE: PLEASE LIST THE BELOW CODES ON ELECTRICAL |
| | PLANS AS THEY ARE BEING PRINTED BELOW. THE PLANS APPEAR |
| | TO TAKE PART OF MY PREVIOUS REVIEW COMMENTS AND PLACE |
| | THIS ON THE SHEETS. PLEASE SEE CODE WHICH SEEMS TO BE |
| | MISPRINT FOR NEPA. PLEASE ONLY INDICATE THE FOLLOWING. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NPPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** SOME ARE OK, HOWEVER NOT ALL AND ONLY MINOR |
| | ADJUSTMENTS ARE NEEDED. PLANS ARE COMING BACK FOR |
| | CORRECTIONS AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE COMPLETE AND CORRELATE ALL CIRCUITING |
| | ON PLANS. PLEASE SEE THAT THERE ARE CIRCUITS ON PLANS |
| | FOR EXAMPLE FOR 120V GFI LOADS WHICH ARE SHOWN |
| | CIRCUITED TO A/C SYSTEM WHICH IS NOT POSSIBLE. PLEASE |
| | SEE FOR EXAMPLE: CIRCUITS 18 AND 19 ON PLANS. PLEASE |
| | SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO THE |
| | NORMAL LIGHTING BRANCH CIRCUITS IN THE AREAS IN WHICH |
| | THEY ARE LOCATED. |
| | FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC |
| | NEC 408.4, 310.16, 240.4. |
| | PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN |
| | DIRECTLY FROM THE NEC. |
| | *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION* |
| | **SAME COMMENT ON TWO PREVIOUS REVIEWS. |
| | |
| | 4) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS |
| | AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR |
| | FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR |
| | FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE |
| | FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY |
| | CARE OCCUPANCIES. |
| | A COMPLETED FIXTURE LEGEND OF FIXTURES IS REQUIRED. FBC |
| | 106.1.2 LS 101 CHAPTER 16. |
| | **SAME COMMENT ON PREVIOUS TWO REVIEWS. |
| | |
| | 5) NOTE:THIS WAS THE SAME COMMENT FROM TWO PREVIOUS |
| | REVIEWS AND YET NO COMPLIANCE WITH FBC CHAPTER 13 OR |
| | CALCULATIONS HAS BEEN SUBMITTED. |
| | PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO MEET THE |
| | 2004 FBC 13-415.1.AB.1. |
| | PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER |
| | DENSITIES PER 13-415.2 |
| | PLEASE SEE THAT NONE WERE SUBMITTED. |
| | PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED |
| | CERTIFICATIONS. |
| | ** SAME AS TWO PREVIOUS REVIEWS. |
| | |
| | 6) NOTE: PLEASE SEE LS-101 16.5.1.2 |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN |
| | TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE |
| | LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH |
| | PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT |
| | PLUGGED IN OR IN USE. |
| | ** SAME AS TWO PREVIOUS REVIEWS. MAY NOT QUOTE THE CODE |
| | OR REQUIREMENT IN LIEU OF ACTUAL DESIGN OR SPECIFIC |
| | DETAILS NEEDED. 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE, |
| | 9.6.4, 16.3.4.5. |
| | PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL |
| | BE SHOWN. |
| | THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING. |
| | PLEASE SEE REVIEW COMMENTS FROM FIRE MARSHAL AS FIRE |
| | ALARM SYSTEM IS REQUIRED. |
| | PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM |
| | LOCATIONS AND DEVICE LEVELS TO MEET ADA. |
| | |
| | |
| | 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR EGRESS |
| | LIGHTING PER 7.8., 7.9. |
| | PLEASE SEE 106.1.2 FBC FOR ADDITIONAL INFORMATION |
| | NEEDED. |
| | |
| | 9) NOTE: THE LOAD CALCULATIONS SUBMITTED ONCE AGAIN ARE |
| | FOR A RESIDENTIAL USE AND NOT FOR COMMERCIAL. PLEASE |
| | REVISE AND CORRECT. |
| | PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC, |
| | THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND |
| | OCCUPANCY. |
| | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, |
| | PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. |
| | 215.3, 230.42 |
| | ** SAME NOTE AS TWO PREVIOUS REVIEWS. |
| | |
| | 10) NOTE: PLEASE SEE THE NOTE #3 ON PANEL SCHEDULE |
| | NOTES MENTIONS * AHU IS NOW- CONCURRENT WITH CONDENSING |
| | UNIT*. |
| | PLEASE VERIFY THIS AS THIS IS MOST LIKELY NOT WHAT IS |
| | MEANT TO BE NOTED. PLEASE SEE 220.60 WHICH IS FOR A/C. |
| | THIS IS EXTRACTED FROM THE NEC BELOW FOR CLARIFICATION |
| | OF CODE. |
| | *220.60 NONCOINCIDENT LOADS |
| | WHERE IT IS UNLIKELY THAT TWO OR MORE NONCOINCIDENT |
| | LOADS WILL BE IN USE SIMULTANEOUSLY, IT SHALL BE |
| | PERMISSIBLE TO USE ONLY THE LARGEST LOAD(S) THAT WILL |
| | BE USED AT ONE TIME FOR CALCULATING THE TOTAL LOAD OF A |
| | FEEDER OR SERVICE.* |
| | |
| | 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| | HEATER. PLANS SHOW A RECEPTACLE WHICH CAN NOT BE USED |
| | FOR CONNECTION OF WATER HEATERS. 422.30, 422.31. |
| | |
| | 12) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER |
| | HEATERS ARE NOW CONSIDERED UNDER THE 2005 NEC AS A |
| | CONTINUOUS LOADS WHICH REQUIRES LOAD TO BE FIGURED AT |
| | 125% IN CALCULATIONS. |
| | PLEASE SEE NOTE # 9 ABOVE AS ALL CALCULATIONS WILL BE |
| | ADJUSTED. |
| | |
| | 13) NOTE: PLEASE PROVIDE ALL LICENSE INFORMATION AS |
| | REQUIRED FOR ALL DESIGNERS ON PLANS AS LICENSED UNDER |
| | FS 481. |
| | PLEASE SEE 481.229 AS *DESIGNERS/DRAFTSPERSONS* NOT |
| | LICENSED UNDER FS 481 MAY NOT DESIGN OR DO COMMERCIAL |
| | WORK AS IN THE SCOPE AS LISTED ON PLANS. |
| | PLEASE ADJUST TITLE BLOCKS WHICH REMOVES THE DESIGNER |
| | AS SHOWN ON INCLUDE THE LICENSE INFORMATION AS REQUIRED |
| | PER FAC61G1-16.004, FS 481. |
| | ** THE COMMENT IS NOT FOR MR. WRONKSKY. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OF THE OTHER |
| | TRADE REVIEWS. |
| | |
| | 14) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM MAIN TO SUB PANEL. |
| | 250.110, 250.24, 250.122 ETC. |
| | |
| | 15) NOTE: PLEASE KNOW WITH RESPECT TO FS 553.80(2)(B), |
| | THE FEE AS REQUIRED BY THE FLORIDA STATUES AS NOTED |
| | WHICH WOULD HAVE BEEN ASSESSED IS NOT ASSESSED DUE TO |
| | NEW DESIGN TEAM. |
| | |
| | ** PLEASE KNOW AS MENTIONED ABOVE, AS THERE WILL BE |
| | SEVERAL CHANGES ON PLANS AND AS THERE ARE SEVERAL ITEMS |
| | NOT SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |