| 2007-05-22 14:04:49 | |
| | |
| | PAUL SCHMITZ |
| | |
| | [email protected] |
| | FBC 2004 PLUMBING CODE |
| | PLAN REVIEW |
| | FBC 2004 FUEL GAS CODE PLAN REVIEW FBC |
| | 2004 CH 11, FL ACCESSIBILITY CODE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE |
| | CHAPT.1, ADMINISTRATION, 2004 |
| | EDITION |
| | |
| | DENIED 2ND |
| | TIME 5-22-07 |
| | "SEE COMMENTS IN CAPITOL |
| | LETTERS" |
| | |
| | NOT ADDRESSED |
| | 1)SHT 3. BOYS & GIRLS REST ROOM |
| | COMPLY WITH 36 CFR PART 1191 [ DOCKET NO.94-2]"GUIDE |
| | LINES" |
| | ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND |
| | FACILITIES; BUILDING ELEMENTS DESIGNED FOR CHILDREN'S |
| | USE. |
| | |
| | SHT 3. LABEL DRINKING FOUNTAIN AS D/F, WHY, 3 W/F |
| | ? |
| | 2) SHT 3.11-4.1.3 (10)DRINKING FOUNTAINS. |
| | (A) WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A |
| | FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS |
| | ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN |
| | ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO |
| | THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A ?HI-LO? FOUNTAIN; |
| | BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE |
| | WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT |
| | CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY |
| | PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15 |
| | AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD |
| | ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON |
| | EACH FLOOR.) |
| | |
| | DIMENSIONS ON BOYS AND GIRLS REST RM, |
| | WIDTH NOT TO SCALE, MIN 5'-2" |
| | 3) SEC. (11) 11-4.1.3 ACCESSIBLE BUILDINGS: NEW |
| | CONSTRUCTION, TOILET FACILITIES. IF TOILET ROOMS ARE |
| | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS |
| | PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES |
| | (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A |
| | PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS |
| | ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM |
| | SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET |
| | ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE |
| | ROUTE. |
| | |
| | WATER PIPING ISOMETRIC NOT INCLUDED |
| | 4) SHT 4. COMPLY WITH SEC 106 SANITARY AND WATER PIPE |
| | ISOMETRIC, INCLUDE PIPE SIZES ON THE ISOMETRICS. |
| | SHT 4 PLUMBING NOTES ARE NOT SUFFICENT TO INDICATE |
| | NATURE OF WORK. |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| | 106.3.5). |
| | |
| | |
| | NOT ADDRESSED |
| | 5)SECTION 608, BACK FLOW PREVENTER |
| | PROTECTION OF POTABLE WATER SUPPLY |
| | 608.1 GENERAL. |
| | A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED, |
| | INSTALLED AND MAINTAINED IN SUCH A MANNER SO AS TO |
| | PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS |
| | OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY |
| | THROUGH CROSS-CONNECTIONS OR ANY OTHER PIPING |
| | CONNECTIONS TO THE SYSTEM. BACKFLOW PREVENTER |
| | APPLICATIONS SHALL CONFORM TO TABLE 608.1, EXCEPT AS |
| | SPECIFICALLY STATED IN SECTIONS 608.2 THROUGH |
| | 608.16.9. |
| | |
| | NOT ADDRESSED |
| | 6) SEC 607.3 THERMAL EXPANSION CONTROL. |
| | A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY |
| | THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN |
| | ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2 |
| | BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A |
| | BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE |
| | IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE |
| | WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION |
| | CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR |
| | CONTROLLING PRESSURE SHALL BE INSTALLED. |
| | |
| | NOT ADDRESSED |
| | 7)SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT |
| | PLUMBING PLAN REVIEW. |
| | |
| | 8) NEW COMMENT:HEALTH DEPARTMENT NOTES, CHILD CHANGE |
| | STATIONS TO BE INCLUDED ON REVISEED PLANS. |
| | |
| | 9) NEW COMMENT: SERVICE AREA IS NOT EXISTING, INCLUDE |
| | ON DWV, WATER ISOMETRIC. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |