| 2007-05-22 17:04:42 | *****DENIED***** |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN |
| | REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL |
| | BE REFERENCED. |
| | |
| | 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS |
| | FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE |
| | REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF |
| | THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE |
| | CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE |
| | DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE |
| | SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER. |
| | |
| | 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE |
| | MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED |
| | AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED |
| | TO SUBSTANTIATE SUCH A MODIFICATION. |
| | |
| | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| | OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR |
| | ROADWAYS). |
| | |
| | 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET. |
| | AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO |
| | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH |
| | CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE |
| | ON THE DOOR) |
| | |
| | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| | THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO |
| | INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY |
| | LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE |
| | EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE. |
| | |
| | 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS |
| | CAN OPEN THE DOOR FROM INSIDE THE CLOSET. |
| | |
| | 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO |
| | ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN |
| | OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE |
| | STAFF. |
| | |
| | 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL |
| | BE CLASS A OR CLASS B. |
| | |
| | 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE |
| | OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH |
| | A FIRE ALARM SYSTEM. |
| | |
| | 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE |
| | DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE |
| | OCCUPANCIES. |
| | |
| | 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | THE CLIENTS. |
| | |
| | 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT, |
| | AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS |
| | ARE PRESENT. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT |
| | WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |