| Date |
Text |
| 2007-05-11 09:16:18 | ** UNSAT2ND REVIEW ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY |
| | CARE FACILITY. |
| | |
| | 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE |
| | FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL |
| | REVIEW. |
| | NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003 |
| | NFPA-101, 2004 FBCW/2006 REVISIONS. |
| | PLEASE SEE MISPRINT ON ELECTRICAL SHEETS ALONG WITH THE |
| | CODE AND ?BUILDING LEVEL? ? BEING SHOWN AS #2? |
| | ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2 |
| | ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE |
| | IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND |
| | CURRENT CODES. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS ARE DONE IN A CLEAR AND |
| | PRINTED MANOR WHICH ARE A MINIMUM OF DRAFTSMAN QUALITY |
| | AS REQUIRED UNDER FBC 106.1.3 |
| | |
| | 3) NOTE:SAME COMMENT, NO INFORMATION SUBMITTED. |
| | PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS AND |
| | CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR FIXTURES |
| | WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR FIXTURES |
| | (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE FIXTURES |
| | SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY CARE |
| | OCCUPANCIES. |
| | PLEASE ALSO SEE THESE LIGHTING FIXTURES AND SCHEDULES |
| | MUST MEET THE FLA-COM CALCULATIONS FOR CHAPTER 13 OF |
| | THE FBC 2004 W/2006 REVISONS. |
| | FBC 106.1.2 LS 101 CHAPTER 16. |
| | |
| | 4) NOTE: SAME NOTE: PLEASE SUBMIT COMPLETE ENERGY |
| | CALCULATIONS TO MEET THE 2004 FBC 13-415.1.AB.1.ETC |
| | PLEASE BE SURE COORDINATE ALL FIXTURES ON PLANS WITH |
| | THAT OF THE FIXTURE SCHEDULE AND CALCULATIONS. PLEASE |
| | ALSO PROVIDE INFORMATION ON LIGHTING POWER DENSITIES |
| | PER 13-415.2 |
| | PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED ARE |
| | METHOD B FOR RESIDENTIAL. THIS IS NOT A RESIDENTIAL |
| | OCCUPANCY AND MAY NOT USE THIS. PLEASE ALSO SEE THAT |
| | WHEN THE CORRECTED CALCULATIONS ARE SUBMITTED, THESE |
| | ARE REQUIRED TO BE SIGNED, DATED AND SEALED AS |
| | PREVIOUSLY STATED AND REQUIRED UNDER THE FBC. PLEASE |
| | ALSO SEE 13-103.1.1.1 FOR REQUIRED CERTIFICATIONS. |
| | |
| | 5) NOTE:SAME NOTE: PLEASE SEE A NOTE WAS ADDED FOR |
| | REQUIRED DEVICES; HOWEVER NO CHANGES WERE MADE TO THE |
| | SYMBOL LEGEND FOR TYPE? ETC. |
| | PLEASE SEE LS-101 16.5.1.2 |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN |
| | TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE |
| | LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH |
| | PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT |
| | PLUGGED IN OR IN USE. |
| | |
| | 5) NOTE: PLEASE CLARIFY THE NEW NOTE #6 WHICH WAS ADDED |
| | TO PLANS. THIS NOTE AND THE CODE SECTION NOTED HAVE |
| | NOTHING TO DO WITH ONE ANOTHER. |
| | PLEASE SEE THE LS CODE STIPULATES THE MINIMUM LEVELS |
| | FOR EGRESS LIGHTING PER 7.8.1.3, 7.9.2.2. |
| | PLEASE SEE THE SECTION OF THE FBC NOTED IS FOR |
| | ADDITIONAL INFORMATION REQUIRED ON PLANS ONLY. |
| | |
| | 6) NOTE: AS RISER HAS NOW CHANGED FROM THAT PREVIOUSLY |
| | SUBMITTED, PLEASE SEE THE PANEL SCHEDULE SHOWS A MCB ( |
| | MAIN CIRCUIT BREAKER) AND THE RISER SHOWS PANEL AS |
| | MLO(MAIN LUG ONLY). PLEASE COORDINATE. |
| | |
| | 7) NOTE: PLEASE SEE THE PLANS APPEAR TO SHOW A PANEL |
| | INSIDE, HOWEVER AS THE PLANS ARE NOT CLEAR, THE |
| | LOCATION IS NOT CONFIRMED. |
| | *IMPORTANT* |
| | PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT |
| | TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES. |
| | (PANELS REQUIRED CONTAINING LOCKABLE COVERS IF INSIDE |
| | BUILDING AND ACCESSIBLE FOR OCCUPANTS. |
| | PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6. |
| | |
| | 8) NOTE:THIS IS THE SAME NOTE. THE LOAD CALCULATIONS |
| | SUBMITTED ARE FOR A RESIDENTIAL USE AND NOT FOR |
| | COMMERCIAL. PLEASE REVISE AND CORRECT. |
| | PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC, |
| | THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND |
| | OCCUPANCY. |
| | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, |
| | PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. |
| | 215.3, 230.42 |
| | |
| | 9) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS |
| | NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE |
| | MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT |
| | MADE AT THIS TIME. |
| | PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |