| Date |
Text |
| 2007-06-04 15:37:16 | BUILDING PLAN REVIEW |
| | PERMIT: 07011175 |
| | ADD: 1115 13TH ST |
| | CONT: ALL-SITE CONSTRUCTION |
| | TEL: (561)317-6959 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. |
| | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION |
| | SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3 ) 2ND REQUEST110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR |
| | CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WILL BE ISSUED. PLAANS SUBMITTED AFTER |
| | 12-08-06 ARE TO BE DESIGNED UNDER THE 2006 FBC NOTE |
| | ALSO REFLECT EXISTING BUILDING CODE 2004/2006 |
| | AMENDMENTS |
| | NOTE CHAPTER 8 FOR CHANGE IN OCCUPANCY 2006 FBC |
| | EXISTING BUILDING |
| | NOTE CHAPTER 9 FOR ADDITIONS 2006 FBC EXISTING BUILDING |
| | CODE |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3.NOTE CHANGE IN |
| | OCCUPANCY. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. RESPONSE INDICATES THE |
| | DESIGN AS TYPE III-B FOR A DAYCARE THE DAYCARE COULD |
| | HAVE 14,500 SQ FT AND 2 STORY, THIS IS A MINIMUM CODE |
| | PLEASE PROVIDE THE CORRECT INFORMATION. |
| | D) THE OCCUPANTLOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | *** THIS INFORMATION IS TO APPEAR ON THE PLANS** |
| | |
| | 4) 2ND REQUEST,THE DECLARED VALUE OF THE PROJECT IS LOW |
| | IN VALUE. IF THE VALUE OF THE PROJECT IS NOT |
| | INCREASED, |
| | THE CITY WILL CALCULATE THE COST OF THE PROJECT USING |
| | MARSHALL & SWIFT FOR CALCULATING PURPOSES |
| | LATEST EDITION. 384 SQ FT X $105.10(ADDITION ALONE)= |
| | $40,359.00.I-4 OCCUPANCY / DAYCARE |
| | SEE CALCULATED FEES + STATE RADON FEES= FEE BALANCE OF |
| | $307.18.2ND REVIEW, M FEES ARE STILL OUTSTANDING. |
| | |
| | 5) 2ND REQUEST, A CHANGE IN OCCUPANCY PLUS ANADDITION |
| | IMPACT FEES ASSESSMENT; |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) 2ND REQUEST,PLANS INDICATE THE USE OF 32" DOORS, |
| | THE 32" POCKET DOORS ARE |
| | CODE COMPLIANTBUT THE OTHER DOORS THAT ARE A 32" DOOR |
| | WILL NOT PROVIDE A 32" OPENING. |
| | |
| | RESTROOM DOORS:11-4.22.2 DOORS. |
| | ALL DOORS TO ACCESSIBLE TOLIET ROOMS SHALL COMPLY WITH |
| | 11-4.13. DOORS SHALL NOT SWING INTO |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCESAT DOORS THAT |
| | ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN |
| | IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | PROVIDE THE CLEAR FLOOR SPACE FOR THE PLUMBING |
| | FIXTURES, HIGHLIGHT THIS AREA, YOU WILL SEE THE |
| | RESTROOM DOORS SWING INTO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR THE FIXTURES!!!!! |
| | |
| | 7) EXISTING BUILDING CODE, 812.5 ACCESSIBILITY. |
| | EXISTING BUILDINGS OR PORTIONS THERREOF THAT UNDERGO A |
| | CHANGE IN OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| | CHAPTER 11 OF THE FLORIDA BUILDING CODE. |
| | |
| | 8) EXISTING BUILDING CODE 905.1 ACCESSIBILITY |
| | PROVISIONS FOR NEW CONSTRUCTION SHALL APPLY TO |
| | ADDITIONS. AN ADDITION THAT AFFECTS THE ACCESSIBILITY |
| | TO OR CONTAIN AN AREA OF, PRIMARY FUNCTION SHALL COMPLY |
| | WITH THE REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 9)2ND REQUEST,PLEASE PROVIDE SITE PLAN INDICATING THE |
| | HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE |
| | ENTRY.11-4.1.1(A)(B) 11-4.1.2(5)(A). SHEET 2 INDICATES |
| | A 44" ACCESS AISLE LEADING FROM THE DISABLED PARKING |
| | SPACE BUT THE PLANS FAIL TO INDICATE A CURB CUT THROUGH |
| | THE4" THICK SIDEWALK. PLANS ALSO FAIL TO INDICATE THE |
| | TOP OF THE ACCESSIBLE SIDE WALK IN REGARDS TO THE |
| | INTERIOR FINISH FLOOR. |
| | |
| | 10)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS SUBMITTED WERE 2001 |
| | |
| | 11 PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | 12)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) COMPLIED. |
| | |
| | 14)2ND REQUEST, 1203.2 ATTIC SPACES. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING |
| | SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE |
| | MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF |
| | AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND |
| | THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL |
| | NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE |
| | VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING |
| | AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER |
| | PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET |
| | (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE |
| | OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE |
| | VENTS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |