| Date |
Text |
| 2007-02-11 10:48:14 | 2007-02-11 10:48:14 |
| | **** UNSAT **** |
| | |
| | |
| | *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY |
| | CARE FACILITY. |
| | |
| | |
| | 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE |
| | FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL |
| | REVIEW. |
| | NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003 |
| | NFPA-101, 2004 FBC. |
| | |
| | ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2 |
| | ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE |
| | IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND |
| | CURRENT CODES. |
| | |
| | 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH A SUBMITTED PANEL SCHEDULE WHICH IS |
| | CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE SEE THE |
| | PANEL SCHEDULE IS NOT CLEAR FOR ITEMS ON PANEL. PLEASE |
| | CORRELATE PLANS AND PANEL SCHEDULE AS THERE ARE |
| | ELECTRICAL ITEMS ON PANEL SCHEDULE WHICH ARE NOT ON |
| | PLANS. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTS. |
| | FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC |
| | NEC 408.4, 310.16, 240.4. |
| | PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN |
| | DIRECTLY FROM THE NEC. |
| | *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION* |
| | |
| | 3) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS |
| | AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR |
| | FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR |
| | FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE |
| | FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY |
| | CARE OCCUPANCIES. |
| | FBC 106.1.2 LS 101 CHAPTER 16. |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO |
| | MEET THE 2004 FBC 13-415.1.AB.1. |
| | PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER |
| | DENSITIES PER 13-415.2 |
| | PLEASE SEE THAT NONE WERE SUBMITTED. |
| | PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED |
| | CERTIFICATIONS. |
| | |
| | 5) NOTE: PLEASE SEE LS-101 16.5.1.2 |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN |
| | TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE |
| | LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH |
| | PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT |
| | PLUGGED IN OR IN USE. |
| | |
| | 5) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE, |
| | 9.6.4, 16.3.4.5. |
| | PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL |
| | BE SHOWN. |
| | THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING. |
| | |
| | 6) NOTE: PLEASE SEE THAT IN NO CASE MAY THERE BE |
| | *WHITE-OUT* OR HAND WRITTEN CHANGES MADE TO PLANS. |
| | PLEASE ALSO SEE THAT PLANS WHICH ARE SIGNED, DATED AND |
| | SEALED SHALL ALSO NOT CONTAIN THESE ITEMS. |
| | FS 481.221 |
| | |
| | 7) NOTE: PLEASE SEE MISSING NEW FOOTER STEEL AS PART OF |
| | THE GROUNDING ELECTRODE SYSTEM PER 250.50. |
| | |
| | 8) NOTE: PLEASE PROVIDE SCHEDULE FOR THE METER/MAIN |
| | COMBO PANEL WHICH DOES NOT INDICATE ANY OVER CURRENT |
| | PROTECTION DEVICES FOR ANY ITEMS FROM THE METER/MAIN. |
| | PLEASE SEE THAT ANY OTHER ELECTRICAL FED ITEMS FROM THE |
| | METER/MAIN PANEL SHALL ALSO BE STATED WITH THE BREAKER |
| | SIZE, CONDUCTOR SIZES ETC. |
| | PLEASE SHOW THE LOCATION OF ALL ELECTRICAL SERVICE |
| | EQUIPMENT LOCATIONS ON ELECTRICAL PLANS. |
| | PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT |
| | TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES. |
| | (PANELS REQUIRED TO CONTAIN LOCKABLE COVERS IF INSIDE |
| | BUILDING AND ACCESSIBLE FOR OCCUPANTS. |
| | PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6. |
| | |
| | 9) NOTE: PLEASE SEE 16.28, 16.29 FOR REQUIRED EMERGENCY |
| | EGRESS LIGHTING WHICH IS REQUIRED TO MEET 7.8 AND 7.9. |
| | PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR EGRESS DOES |
| | NOT SEEM TO BE ACCOMPLISHED AT THIS TIME FOR THE |
| | LOCATION AND NUMBER OF FIXTURES SHOWN ON PLANS. PLEASE |
| | SEE A MINIMUM OF 1FT CANDLE IS REQUIRED AT ALL EGRESS |
| | PATHS/LEVELS OF WALKING SURFACE. |
| | THIS CAN BE ACCOMPLISHED BY PROVIDING PHOTO-METRICS FOR |
| | VERIFICATION OF MINIMUM LIGHTING LEVELS. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE PROVIDE THE SERVICE ENTRANCE |
| | CONDUCTORS ON RISER. |
| | 240.4, 310.16 ETC. THIS IS CONSIDERED COMMERCIAL. |
| | |
| | 11) NOTE: PLEASE SEE THE LOAD CALCULATIONS SHALL MEET |
| | 2005 NEC, THESE ARE SUBMITTED AND SHOWN FOR DWELLING |
| | USE AND OCCUPANCY. |
| | PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, |
| | PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. |
| | 215.3, 230.42 |
| | |
| | 12) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS *ALL PANELS |
| | (1,2 AND 3) ARE EQUIPPED WITH FUSIBLE DISCONNECT* , |
| | THIS IS NOT CLEAR AS OTHER INFORMATION MENTIONS MAIN |
| | CIRCUIT BREAKER EQUIPMENT. |
| | PLEASE CLARIFY. |
| | FBC106.1.21 |
| | |
| | 13) NOTE: PLEASE SEE 600.5 A AND B. |
| | |
| | 14) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS |
| | NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE |
| | MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT |
| | MADE AT THIS TIME. |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |