| 2007-03-05 09:50:10 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3)THE INFORMATION ON THE SHUTTER SCHEDULE DOES NOT |
| | MATCH THE ANY OF THE PRODUCT APPROVAL SUBMITTED. THE |
| | OPENING DIMENTIONS ON THE SCHEDULE DOES NOT CORRESPOND |
| | WITH THE DIMENTIONS ON THE DRAWINGS CLARITY. |
| | |
| | 4)WPB AMENDMENTS 106.3.3.THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | PROVIDE THE FLORIDA STATE APPROVAL COVER PAGES FOR THE |
| | PRODUCT APPROVALS. |
| | |
| | 5)SUBMIT AN ELEVATION FRAMING DETAIL OF THE NORTH / |
| | SOUTH / EAST AND WEST ELEVATIONS. SEE WPB. AMENDMENTS |
| | 106.3.5 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |