Plan Review Notes
Plan Review Notes For Permit 07011148
Permit Number 07011148
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-13 17:11:01 
  
  
 PLANS EXAMINER: KEN CONRAD
 PROJECT: 250 SOUTH AUSTRALIAN/SUITE 300
 FL. BLDG. CODE: FLORIDA EXISTING BUILDING CODE/FLORIDA
 BUILDING CODE WITH 2006 REVISIONS
 PERMIT# 07011148
 PHONE: 561. 805.6666
  
 2ND REVIEW
 STATUS: DENIED
  
  
  
 COMMENTS:
  
 1) SHEET A-1, PROJECT INFORMATION INDICATES 2004 FBC.
 THE PROJECT INFORMATION SHOULDALSO INDICATE 2005/2006
 REVISIONS AND THE EXISTING BUILDING CODE WITH THE 2006
 REVISIONS AS PER THE WEST PALM BEACH ADMINISTRATIVE
 CODE, SECTION 110.1.2.
  
 2) ITEMS A THROUGH F HAVE NOT BEEN ADDRESSED FROM THE
 PREVIOUS PLAN REVIEW.
  
 3) PLEASE NOTE OCCUPANCY LOAD ON THE LIFE SAFETY PLAN.
  
 4) MISSING EXIT LIGHTS ON REVISED SHEETS A-5 AND A-10:
  
 1006.3.8
 WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT
 IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH
 SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A
 SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR
 SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN
 EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED.
  
 5) PLEASE INDICATE THE LEVEL OF ALTERATION WITHIN THE
 PROJECT INFORMATION LOCATED ON SHEET A-1 AS REQUIRED BY
 THE FEBC SECTION 301.5.
  
 6) REQUIRE APPLICABLE THROUGH PENETRATION FIRE-STOP
 ASSEMBLIES AT FIRE -RATED PARTITIONS:
  
 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 7) PROVIDE INTERIOR FLOOR FINISH DOCUMENTATION AS PER
 THE FOLLOWING SECTIONS:
  
 FEBC603.4INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND CEILINGS IN EXITS AND
 CORRIDORS IN ANY WORK AREA SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 EXCEPTION: EXISTING INTERIOR FINISH MATERIALS THAT DO
 NOT COMPLY WITH THE INTERIOR FINISH REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING SHALL BE PERMITTED TO
 BE TREATED WITH AN APPROVED FIRE-RETARDANT COATING IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS TO
 ACHIEVE THE REQUIRED RATING.
  
 804.2 CLASSIFICATION.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS
 REQUIRED BY SECTION 804.5.1 TO BE OF CLASS I OR II
 MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH NFPA
 253. THE CLASSIFICATION REFERRED TO HEREIN
 CORRESPONDS TO THE CLASSIFICATIONS DETERMINED BY NFPA
 253 AS FOLLOWS: CLASS I, 0.45 WATTS/CM2 OR GREATER;
 CLASS II, 0.22 WATTS/CM2 OR GREATER.
  
 804.3 TESTING AND IDENTIFICATION.
 FLOOR COVERING MATERIALS SHALL BE TESTED BY AN APPROVED
 AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A
 HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE
 MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE
 THE INTERIOR FLOOR FINISH OR FLOOR COVERING
 CLASSIFICATION ACCORDING TO SECTION 804.2. CARPET-TYPE
 FLOOR COVERINGS SHALL BE TESTED AS PROPOSED FOR USE,
 INCLUDING UNDERLAYMENT. TEST REPORTS CONFIRMING THE
 INFORMATION PROVIDED IN THE MANUFACTURER?S PRODUCT
 IDENTIFICATION SHALL BE FURNISHED TO THE BUILDING
 OFFICIAL UPON REQUEST.
  
 8)PROVIDE TACTILE SIGNAGE AT EXIT STAIR DOOR:
  
 1006.3.4 EXIT STAIR DOOR OR TACTILE
 SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.