| Date |
Text |
| 2007-06-13 17:11:01 | |
| | |
| | |
| | PLANS EXAMINER: KEN CONRAD |
| | PROJECT: 250 SOUTH AUSTRALIAN/SUITE 300 |
| | FL. BLDG. CODE: FLORIDA EXISTING BUILDING CODE/FLORIDA |
| | BUILDING CODE WITH 2006 REVISIONS |
| | PERMIT# 07011148 |
| | PHONE: 561. 805.6666 |
| | |
| | 2ND REVIEW |
| | STATUS: DENIED |
| | |
| | |
| | |
| | COMMENTS: |
| | |
| | 1) SHEET A-1, PROJECT INFORMATION INDICATES 2004 FBC. |
| | THE PROJECT INFORMATION SHOULDALSO INDICATE 2005/2006 |
| | REVISIONS AND THE EXISTING BUILDING CODE WITH THE 2006 |
| | REVISIONS AS PER THE WEST PALM BEACH ADMINISTRATIVE |
| | CODE, SECTION 110.1.2. |
| | |
| | 2) ITEMS A THROUGH F HAVE NOT BEEN ADDRESSED FROM THE |
| | PREVIOUS PLAN REVIEW. |
| | |
| | 3) PLEASE NOTE OCCUPANCY LOAD ON THE LIFE SAFETY PLAN. |
| | |
| | 4) MISSING EXIT LIGHTS ON REVISED SHEETS A-5 AND A-10: |
| | |
| | 1006.3.8 |
| | WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT |
| | IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH |
| | SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A |
| | SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR |
| | SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN |
| | EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED. |
| | |
| | 5) PLEASE INDICATE THE LEVEL OF ALTERATION WITHIN THE |
| | PROJECT INFORMATION LOCATED ON SHEET A-1 AS REQUIRED BY |
| | THE FEBC SECTION 301.5. |
| | |
| | 6) REQUIRE APPLICABLE THROUGH PENETRATION FIRE-STOP |
| | ASSEMBLIES AT FIRE -RATED PARTITIONS: |
| | |
| | 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| | |
| | 7) PROVIDE INTERIOR FLOOR FINISH DOCUMENTATION AS PER |
| | THE FOLLOWING SECTIONS: |
| | |
| | FEBC603.4INTERIOR FINISH. |
| | THE INTERIOR FINISH OF WALLS AND CEILINGS IN EXITS AND |
| | CORRIDORS IN ANY WORK AREA SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | EXCEPTION: EXISTING INTERIOR FINISH MATERIALS THAT DO |
| | NOT COMPLY WITH THE INTERIOR FINISH REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING SHALL BE PERMITTED TO |
| | BE TREATED WITH AN APPROVED FIRE-RETARDANT COATING IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS TO |
| | ACHIEVE THE REQUIRED RATING. |
| | |
| | 804.2 CLASSIFICATION. |
| | INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS |
| | REQUIRED BY SECTION 804.5.1 TO BE OF CLASS I OR II |
| | MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH NFPA |
| | 253. THE CLASSIFICATION REFERRED TO HEREIN |
| | CORRESPONDS TO THE CLASSIFICATIONS DETERMINED BY NFPA |
| | 253 AS FOLLOWS: CLASS I, 0.45 WATTS/CM2 OR GREATER; |
| | CLASS II, 0.22 WATTS/CM2 OR GREATER. |
| | |
| | 804.3 TESTING AND IDENTIFICATION. |
| | FLOOR COVERING MATERIALS SHALL BE TESTED BY AN APPROVED |
| | AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A |
| | HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE |
| | MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE |
| | THE INTERIOR FLOOR FINISH OR FLOOR COVERING |
| | CLASSIFICATION ACCORDING TO SECTION 804.2. CARPET-TYPE |
| | FLOOR COVERINGS SHALL BE TESTED AS PROPOSED FOR USE, |
| | INCLUDING UNDERLAYMENT. TEST REPORTS CONFIRMING THE |
| | INFORMATION PROVIDED IN THE MANUFACTURER?S PRODUCT |
| | IDENTIFICATION SHALL BE FURNISHED TO THE BUILDING |
| | OFFICIAL UPON REQUEST. |
| | |
| | 8)PROVIDE TACTILE SIGNAGE AT EXIT STAIR DOOR: |
| | |
| | 1006.3.4 EXIT STAIR DOOR OR TACTILE |
| | SIGNAGE. |
| | TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH |
| | ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR |
| | ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL |
| | BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60 |
| | INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER |
| | LINE OF THE SIGN. |