2007-02-24 16:01:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. APPLICATION INDICATES WORK IN SUITE 200. SHT A-3
 INDICATES WORK ON THE 3RD FLOOR. INDICATE ALL
 SUITES/FLOORS THAT WILL BE INVOLVED IN THE WORK FOR
 THIS PERMIT ON THE APPLICATION. SECTION 105.3.1.
  
 2. FBC-2004 PLUMBING SHALL BE INDICATED WITH OTHER
 APPLICABLE CODES ON SHT A-1.
  
 3. ALL SHEETS. THE ADDRESS FOR THE ARCHITECTURAL
 BUSINESS SHOWN ON THE TITLE BLOCK DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE DBPR WEBSITE. PLEASE UPDATE
 THE DBPR WEBSITE OR SHOW THE CORRECT ADDRESS IN THE
 TITLE BLOCK.--THE TITLE BLOCK MUST SHOW THE
 BUSINESS LICENSE NUMBER. FAC 61G1-16.004(1)(2) & FS
 481.219 481.2055--(SEE ATTACHED SHEETS FROM DBPR
 WEBSITE).
  
 4. SHT A-11 DETAIL SHOW COMPLIANCE WITH THE FOLLOWING:
  
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED MAXIMUM 19" UNDERNEATH THE SINK. SHOW ON SHTS
 A-7 & A-15) - (CABINET DOORS NOT ALLOWED).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES.
 E. 11-4.24.7 FAUCETS
  
 5. SHT P-1 POTABLE WATER RISER INDICATES THE HOT WATER
 TO THE SINK ON THE RIGHT SIDE OF THE FIXTURE. SECTION
 607.4 REQUIRES THE HOT TO BE ON THE LEFT SIDE OF THE
 FIXTURE.- -IF THE REFRIDGERATORS HAVE ICE MAKERS,
 THEN A WATER HAMMER ARRESTOR SHALL BE REQUIRED NEAR THE
 FIXTURES PER SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]