Plan Review Notes
Plan Review Notes For Permit 07011148
Permit Number 07011148
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-23 11:08:47*** DENIED ***
 1) SEE PLANS PAGES M-1, M-2, AND M-3, YELLOW
 HIGH-LIGHTED WALLS ARE ONE HOUR FIRE RATED WALLS AND
 A/C DUCT WORK PENETRATING THEM WILL NEED FIRE DAMPERS
 AND COMPLY WITH 2004 FBC/M 607, PLEASE CORRECT.
  
 2) PLEASE SHOW ON MECHANICAL PLANS HOW THE RETURN AIR
 IS TO PASS THROUGH THE FIRE RATED WALLS, AND COMPLY
 WITH 2004 FBC/M 607.
  