| Plan Review Notes For Permit 07011148 |
| Permit Number |
07011148 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-23 11:08:47 | *** DENIED *** | | | 1) SEE PLANS PAGES M-1, M-2, AND M-3, YELLOW | | | HIGH-LIGHTED WALLS ARE ONE HOUR FIRE RATED WALLS AND | | | A/C DUCT WORK PENETRATING THEM WILL NEED FIRE DAMPERS | | | AND COMPLY WITH 2004 FBC/M 607, PLEASE CORRECT. | | | | | | 2) PLEASE SHOW ON MECHANICAL PLANS HOW THE RETURN AIR | | | IS TO PASS THROUGH THE FIRE RATED WALLS, AND COMPLY | | | WITH 2004 FBC/M 607. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|